Make-Up Water

General

A minimum water flow must be distributed over the adiabatic pre-cooler pads during adiabatic operation. Make-up flow rates
are listed in Table 3. Proper flow is preset using a pressure reducing valve and constant flow valve, as shown in Figure 3.

Make-up Water Connection

Refer to the unit submittal package for specific water connection type, size, and location.
TrilliumSeries™ Adiabatic Cooler - TRF Operation & Maintenance Manual – Component Information & Maintenance
Model Number
TRF-1010N-C80XX17E
TRF-1014N-C80XX26E
TRF-1018N-C80XX34E
TRF-1022N-C80XX43E
TRF-1026N-C80XX51E
TRF-1030N-C80XX60E
TRF-1034N-C80XX68E
TRF-1038N-C80XX77E
Table 3. Make-up Water Flow Rate per Model Number
Figure 3. Make-Up Water Connection Detail
Make-up
Water Flow
# of Fans
Rate
GPM
L/min
4
5.3
20
6
7.9
30
8
10.6
40
10
13.2
50
12
15.9
60
14
18.5
70
16
21.2
80
18
23.8
90
1 Make-up water connection (qty. 1)
2 Pressure reducing valve (qty. 1)
3 Solenoid valve (qty. 2)
4 Constant flow valve (qty. 2)