Fan and Motor

General

This unit utilizes electronically commutated (EC) axial fan and motor assemblies with integrated speed controller and guard
grill. Fans must rotate without obstruction in the direction indicated by arrows on the equipment. If the unit control type is
customer input the fans will stop when the input signal is within the signal range listed in Table 4. Fans must be started up and
operated at full speed for at least three hours once a month to move the bearings and allow any condensate that may have
ingressed to evaporate.
subject the guard grill to load. Do not place any objects on the fan guard grill.
off. Wait five minutes after disconnecting the voltage at all poles before opening the fan and motor
assembly.
resistant safety gloves. The fan is only to be transported in its original packaging. The fan is to be
transported lying flat, i.e., the motor axis must be vertical. Secure the fan(s) e.g., with a lashing strip to stop
anything from slipping or tipping.
sufficient protection against accidental contact.
TrilliumSeries™ Adiabatic Cooler - TRF Operation & Maintenance Manual – Component Information & Maintenance
Signal Type
4-20mA
0-10V
10-0V
BMS 0-100%
Table 4. Input Signal Zero Fan Speed Signal Range
: Rotating equipment. Risk of serious injury or death. Never step on fan guard grill or
: Risk of electric shock. Live terminals and connections even with device switched
: Transporting the fan. Injuries from tipping or slipping. Wear safety shoes and cut-
: High temperature on fan motor electronics housing. Risk of burns. Ensure
0 RPM Fan Speed Signal Range
4mA – 4.8mA
0V – 0.05V
10V – 9.95V
0% - 5%