Headless HMI

The control panel is equipped with a headless HMI feature allowing a user to view the HMI on an external device. Follow the
below instructions to utilize the headless HMI feature.
1.
Navigate to Settings menu, Setup Page 3 of 3 as shown in Figure 65.
a.
Note the IP Address shown on the screen.
2.
Connect a RJ45 cable from an external device to the control panel via the bulkhead at the bottom on the control
panel.
3.
On the external device open a web browser and enter the IP Address followed by ":1011".
4.
Allow TwinCAT HMI to load and go to the Home Screen.
TrilliumSeries™ Adiabatic Cooler - TRF Operation & Maintenance Manual – User Interface
Figure 80. Settings Menu, Technician Page 2 of 2 Fan Detect
Page | 91