Chemical conditioners must ensure complete deoxygenation of the water, contain specific
protective agents for yellow metals (copper and its alloys), anti-scaling agents for lime-
stone, neutral PH stabilizers and, in low-temperature systems, specific biocides for use in
heating systems.
Recommended chemical conditioners:
SENTINEL X100 and SENTINEL X200
FERNOX F1 and FERNOX F3
The unit is equipped with a frost protection system that activates the boiler in heating mode
when the system flow water temperature falls below 6°C. The device is not active if the
power and/or gas supply to the unit is turned off. If necessary, to protect the system use a
suitable antifreeze liquid that meets the above requirements and provided for by UNI 8065.
In the presence of adequate chemical/physical system and feed water treatments and re-
lated high cyclicity controls able to ensure the required parameters, for industrial process
applications the product can be installed in open-vessel systems with vessel hydrostatic
height able to ensure compliance with the minimum operating pressure indicated in the
product technical specifications.
The presence of deposits on the boiler exchange surfaces due to non-compliance
with the above requirements will involve non-recognition of the warranty.
335
EN
cod. 3541V484 - Rev 00 - 07/2022