Sensor - Placement And Confirming Location (Test) - Lennox 21L07 Installation Instructions Manual

Wireless sensor and repeater kits
Hide thumbs Also See for 21L07:
Table of Contents

Advertisement

Sensor – Placement and Confirming
Location (Test)
The wireless sensor has a test functionality to
confirm placement of the sensor is acceptable
range of the RTU. To test the sensor placement:
1. Take the sensor to the desired location.
2. Hold the beaconing button for five seconds
and release.
3. Observe the battery status (battery powered
units only) and signal strength LED (see Table
1. Sensor LED Descriptions).
NOTE: Wait 5 to 20 seconds for the test to com-
pete and observe the status of the battery
(if applicable) and signal strength LED
Table 1. Sensor LED Descriptions
Battery LED
Indicator
Off
Blinking for 10
seconds
Signal
Description
LED
Battery is good, and
3 Blinks
sensor is within range.
Sensor is good to install.
Sensor is within range,
3 Blinks
but battery power is low.
Replace battery.
Table 1. Sensor LED Descriptions
Battery LED
Blinking for 10
seconds
Off
Off
In terms of BLE signal strength, in the technician
application the following is display for signal
strength:
Out of range: <= -88 dBm
Low RSSI: -71 to -87 dBm
Fair RSSI: -56 to -70 dBm
Good RSSI: >= -55 dBm
17
Signal
Indicator
Description
LED
Battery power is low,
and sensor is out of
Solid for 10
range. Move sensor
seconds
closer and replace
batteries.
Battery is good, but
Solid for 10
sensor is not within
seconds
range. Re-Test, or find a
closer location.
Sensor does not have
Off
power. Power sensor
and re-test.

Advertisement

Table of Contents
loading

This manual is also suitable for:

21l09Lcs-5030106924-01106926-01

Table of Contents