Sensor – Wireless Standalone
Standalone operation is a setup of one CORE Unit
Controller and up to five wireless sensors without
a Building Automation System (BAS).
NOTE: The following S1 and S2 switches should
be set before power is applied to the sen-
sor.
STAND ALONE AND BLE
1. Set S1 (switch 6) the MODE switch to ON to
enable STAND ALONE operation.
2. Set S2 (switch 3) OPERATION MODE switch
to OFF to enable wireless BLE operation.
3. Download the CORE Service App and use the
following procedure:
a.
Using the CORE Service App, go to the
Rooftop Unit menu and select Network
Integration under Setup.
b.
Select the Network Setup Wizard.
SETTINGS
c.
Select S-Bus / Wireless Sensor under
Network Setup Wizard and select Next.
d.
Leave the S-Bus address in its current
setting and select Next.
e.
Select the Control Source as Room
Sensor then select Next.
f.
Select CO2 sensor source as Local or
None.
g.
Select Relative Humidity Sensor
Source as Network and select Next.
h.
Select Temperature Sensor Source as
Network and select Next.
i.
Set Occupied Blower Mode as Auto
cycling/Continuous depending on
ventilation need and select Next.
Select Backup Mode as None/Wired
j.
Thermostat/Return Air Backup and
then select Next.
k.
The summary is displayed and then
select Next after verifying the displayed
setting information.
Select Finish.