Sensor - Wireless Installation Setup - Lennox 21L07 Installation Instructions Manual

Wireless sensor and repeater kits
Hide thumbs Also See for 21L07:
Table of Contents

Advertisement

Sensor – Wireless Installation Setup
Wireless operation is ONLY compatible with M4
Unit Controller). To commission a wireless sensor,
you must first pair the CORE Service App to the
applicable RTU.
After the App is connected to the RTU, and the
sensor search process has begun (step 3), you
can leave the range of the RTU and provision
sensors in the space.
IMPORTANT
Sensors MUST be added prior to the repeaters,
otherwise power needs to be removed from the
repeaters before adding the sensors.
1. Open the CORE Service App and navigate
to RTU Menu > Network Integration >
Wireless Sensor Network Setup > Wireless
Sensor Network.
NOTE: Provisioning the RTU is only required
once. If you have already completed this
step, proceed to step 3. Select Adding,
and wait for the adding process to com-
plete.
2. Click Add node on the Network Nodes
screen. This triggers the CORE Service App
to scan for new sensors or repeaters.
3.
Press and hold for two seconds the "Beacon
button" on the side of the wireless sensor.
4.
The MAC address of the wireless sensor
should be visible now on the CORE Service
App.
NOTE: The wireless sensor MAC address can
be verified with the label affixed to the
cover of the sensor.
5. Optionally, name the sensor. Otherwise follow
the prompts on the screen to finish the setup
process.
6.
Verify that the CORE Service App displays the
"Node Provisioned" on the Provision Sensor
Network.
IMPORTANT
DO NOT interrupt the adding process of the
wireless sensors. If interrupted the sensor will
need to be factory-reset.
Maximum of five wireless sensors can be
provisioned per RTU
15

Advertisement

Table of Contents
loading

This manual is also suitable for:

21l09Lcs-5030106924-01106926-01