Flueing Arrangement For Vertical Terminations - Regency Fireplace Products Greenfire GF900C Owners & Installation Manual

Hide thumbs Also See for Greenfire GF900C:
Table of Contents

Advertisement

FLUEING ARRANGEMENT FOR VERTICAL TERMINATIONS

Vertical Flueing with One(1) 90
The shaded area in the diagram shows all allowable combinations
of straight vertical and offset to vertical terminations, using two
45
elbow, with Rigid Pipe Flueing Systems.
o
Flue must be supported at offsets.
Maintain clearances to combustibles as listed in the
"Clearances" section.
Horizontal flue must be supported every 3 feet.
Firestops are required at each floor level and whenever
passing through a wall.
Must use optional rigid pipe adaptor (Part# 510-994)
when using rigid pipe flue systems.
Refer to the "Flue Restrictor Position" section for details
on how to change the flue restrictor from the factory
setting of Set 0 to Set 1 or Set 2 if required.
"THIS UNIT MUST ALWAYS
TERMINATE / FLUE
DIRECTLY TO THE OUTDOORS."
Regency GF900C-2 Gas Fireplace
Elbows (1 - 90
2 - 45
o
o =
)
o
N
OTE: Restrictor settings
Propane: Set #2 - 18mm
ULPG: Set#1 - 26mm
Restrictor Set #3
15mm open
installation
29

Advertisement

Table of Contents
loading

Table of Contents