Huawei UPS5000-H-400 kVA User Manual page 70

Hide thumbs Also See for UPS5000-H-400 kVA:
Table of Contents

Advertisement

UPS5000-H-(400 kVA-800 kVA)
User Manual (100 kVA Power Module)
Figure 6-6 800 kVA cabinet copper bar layout and specifications (unit: mm)
(1) Battery wiring busbar
(4) Busbar of the same power
source for mains and bypass
inputs
If multiple UPSs are connected in parallel, input and output power cables as well
as copper bars for each UPS should have the same length and specifications.
The cables need to be selected according to the site survey data. The cable
recommendation is for your reference only.
Table 6-2 Recommended power cable cross-sectional areas (200–500 kVA)
Item
Mains
input
Bypass
input
Issue 02 (2021-04-22)
NO TICE
Mains input
current (A)
Recomme
nded
cross-
sectional
area
2
(mm
)
Bypass input
current (A)
Recomme
nded
Copyright © Huawei Technologies Co., Ltd.
(2) PE wiring busbar
(5) Bypass input wiring busbar (6) Output wiring busbar
200 kVA
300 kVA
372
557
L1
2 x 95
2 x 150
L2
2 x 95
2 x 150
L3
2 x 95
2 x 150
N
2 x 95
2 x 150
PE
95
150
304
456
L1
2 x 95
2 x 150
6 Installation
(3) Mains input wiring busbar
400 kVA
500 kVA
743
929
2 x 240
3 x 185
2 x 240
3 x 185
2 x 240
3 x 185
2 x 240
3 x 185
240
240
608
760
2 x 240
3 x 185
62