Huawei UPS5000-H-400 kVA User Manual page 72

Hide thumbs Also See for UPS5000-H-400 kVA:
Table of Contents

Advertisement

UPS5000-H-(400 kVA-800 kVA)
User Manual (100 kVA Power Module)
Item
Equipote
ntial
ground
point
Table 6-3 Recommended power cable cross-sectional areas (600–800 kVA)
Item
Mains input
Mains input current (A)
Recommended
cross-sectional
area (mm
Bypass input
Bypass input current (A)
Recommended
cross-sectional
area (mm
Output
Output current (A)
Recommended
cross-sectional
area (mm
Battery input
Nominal battery
(lead-acid
discharge current (A)
battery)
Maximum battery
discharge current (A)
Recommended
cross-sectional
area (mm
Issue 02 (2021-04-22)
Recommended
cross-sectional
2
area (mm
)
600 kVA
1115
L1
4 x 185
L2
4 x 185
2
)
L3
4 x 185
N
4 x 185
PE
240
912
L1
4 x 185
L2
4 x 185
2
)
L3
4 x 185
N
4 x 185
PE
240
912
U
4 x 185
V
4 x 185
2
)
W
4 x 185
N
4 x 185
PE
240
1330
1593
+
4 x 185
-
4 x 185
2
)
PE
240
Copyright © Huawei Technologies Co., Ltd.
200 kVA
300 kVA
16
700 kVA
1300
4 x 240
4 x 240
4 x 240
4 x 240
240
1064
4 x 240
4 x 240
4 x 240
4 x 240
240
1064
4 x 240
4 x 240
4 x 240
4 x 240
240
1551
1858
4 x 240
4 x 240
240
6 Installation
400 kVA
500 kVA
800 kVA
1486
4 x 240
4 x 240
4 x 240
4 x 240
240
1215
4 x 240
4 x 240
4 x 240
4 x 240
240
1215
4 x 240
4 x 240
4 x 240
4 x 240
240
1773
2123
4 x 240
4 x 240
240
64