Firmware Upgrade - ABB Scalable I/O Applications Manual

Table of Contents

Advertisement

4 Software commissioning

4.6 Firmware upgrade

4.6 Firmware upgrade
Upgrade firmware from RobotStudio
Continues on next page
76
Note
Firmware upgrade is not available for Safe digital base devices or for attached
Add-ons.
1 Set the OmniCore controller in manual mode.
2 If the device is in the running state, deactivate Scalable I/O on the
FlexPendant:
a On the start screen, tap I/O, and then select I/O Devices from the menu.
b Select the device and and tap Deactivate.
3 Start RobotStudio and connect to the OmniCore controller.
4 Request write access.
5 In the I/O System tree, right-click the target I/O device and select Upgrade.
xx1900001181
6 The Firmware Upgrade Local I/O Device window is displayed.
Note
The Firmware location field displays the default firmware file. To select a
new firmware file, click the ... button and browse to the folder with the new
firmware file.