I-7018(R)
8-channel Analog Input Module
 Introduction
The I-7018/M-7018 is an 8-channel Analog Input module that provides
current and voltage input, as well as thermocouple input. The I-7018R/
M-7018R is an upgraded version of the I-7018/M-7018 that includes an
extremely high-quality protection mechanism where the overvoltage
protection can be as high as 240 Vrms. The I-7018R/M-7018R is more
suitable for critically harsh environments, and the newly-added open
thermocouple detection feature makes the I-7018R/M-7018R more attractive
than ever. The I-7018/M-7018/I-7018R/M-7018R also features 4 kV ESD
protection and 3000 V
intra-module isolation. The specifications for the
DC
M-7018 and M-7018R are the same as the I-7018 and I-7018R, but provide
additional support for the Modbus RTU protocol as well as the DCON
protocol.
 System Specifi cations
Model
I-7018
Communication
Interface
RS-485
No (Usually supplied by the RS-485 Master. Alternatively,
Bias Resistor
add a tM-SG4 or SG-785.)
Format
(N, 8, 1) (N, 8, 2) (E, 8, 1) (O, 8, 1)
Baud Rate
1200 to 115200 bps
Protocol
DCON
Dual Watchdog
Yes, Module (1.6 Seconds), Communication (Programmable)
LED Indicators/Display
System LED Indicator
Yes, 1 as Power/Communication Indicator
I/O LED Indicators
-
7-segment LED Display
-
Isolation
Intra-module Isolation,
3000 V
DC
Field-to-Logic
EMS Protection
ESD (IEC 61000-4-2)
±4 kV Contact for each Terminal
EFT (IEC 61000-4-4)
±4 kV to Power
Surge (IEC 61000-4-5)
±0.5 kV for Power Line
Power
Reverse Polarity Protection Yes
Input Range
+10 ~ +30 V
Consumption
1.0 W
Mechanical
Dimensions (L x W x H)
123 mm x 72 mm x 35 mm
Installation
DIN-Rail or Wall Mounting
Environment
Operating Temperature
-25 to +75°C
Storage Temperature
-40 to +85°C
Humidity
10 to 95% RH, Non-condensing
ICP DAS CO., LTD
M-7018(R)
I-7018R
M-7018
M-7018R
Modbus RTU, DCON
DC
Website: http://www.icpdas.com
Features
I-7018
±120 V
Overvoltage Protection
DC
8-channel Diff erential or 6-channel Diff erential and
2-channel Single-ended Analog Input
I-7018R and M-7018R
Overvoltage Protection can be up to 240 V
8-channel Diff erential Analog Input
Current, Voltage or Thermocouple Input
3000 V
Intra-module Isolation
DC
Dual Watchdog
Wide Operating Temperature Range: -25 to +75°C
 Applications
• Building Automation
• Machine Automation
• Factory Automation
• Remote Maintenance
 I/O Specifi cations
Model
I-7018
Analog Input
6 Diff erential
and 2
Channels
Single-ended,
or 8 Diff erential
Wiring
Diff erential
Thermocouple J, K, T, E, R, S, B, N, C
Sensor
Voltage
±15 mV, ±50 mV, ±100 mV, ±500 mV, ±1 V, ±2.5 V
Types
±20 mA, 0 ~ +20 mA, +4 ~ +20 mA
Current
(requires an optional external 125 Ω resistor)
Resolution
16-bit
Accuracy
0.1% of FSR
Sampling Rate
10 Hz (Total)
Input Impedance
> 400 kΩ
Common Voltage Protection 25 V
DC
Individual Channel
-
Confi guration
Overvoltage Protection
±120 V
DC
Open Wire Detection
-
(for thermocouple only)
Temperature Outputs
-
Consistency
Stable Temperature Output
-
in the Field
Note 1: For highly-accurate thermocouple measurement, ICP DAS recommends selecting
the I-7018Z/I-7019Z module,which features automatic cold-junction compensation
for each channel, ensuring consistent and stable temperature output.
Note 2: Firmware version B4.2 or later.
Note 3: Firmware version B4.5 or later.
 Thermocouple Type
Type Code
Thermocouple Type
0E
J
0F
K
10
T
11
E
12
R
13
S
14
B
15
N
16
C
17
L
18
M
19
L2
DIN43710
Vol.
2019.12
rms
• Remote Diagnosis
• Testing Equipment
I-7018R M-7018
M-7018R
6 Diff erential
8
and 2
8
Diff erential
Single-ended,
Diff erential
or 8 Diff erential
200 V
25 V
200 V
DC
DC
DC
Yes *Note2 -
Yes *Note3
240 V
±120 V
240 V
rms
DC
rms
Yes
-
Yes
Temperature Range
-210 to +760°C
-270 to +1372°C
-270 to +400°C
-270 to +1000°C
0 to +1768°C
0 to +1768°C
0 to +1820°C
-270 to +1300°C
0 to +2320°C
-200 to +800°C
-200 to +100°C
-200 to +900°C
1/2

Advertisement

loading

Summary of Contents for ICP DAS USA I-7018 CR

  • Page 1 Features I-7018  ±120 V Overvoltage Protection  8-channel Diff erential or 6-channel Diff erential and  2-channel Single-ended Analog Input I-7018R and M-7018R  Overvoltage Protection can be up to 240 V  8-channel Diff erential Analog Input  Current, Voltage or Thermocouple Input ...
  • Page 2  Pin Assignments I-7018 I-7018R/M-7018/M-7018R  Wire Connections  Ordering Information I-7018/I-7018R/M-7018/M-7018R 8-channel Analog Input Module using the DCON I-7018 CR Protocol (Blue Cover) (RoHS) Analog Input Channels 0 to 5 8-channel Analog Input Module using the DCON I-7018-G CR Vinx+ Vinx+...

This manual is also suitable for:

I-7018-g crI-7018r crI-7018r-g crM-7018-g cr