Ice Machine Clearance Requirements
Top/Sides
Back
*NOTE: The ice machine may be built into a cabinet.
There is no minimum clearance requirement for the
top or left and right sides of the ice machine. The listed
values are recommended for efficient operation and
servicing only.
Ice Machine Heat of Rejection
Series
Ice Machine
SM50
QM20
QM30
QM45
Q130
Q170
Q210
Q270
* B.T.U./Hour
** Because the heat of rejection varies during the ice making cycle,
the figure shown is an average.
Ice machines, like other refrigeration equipment, reject
heat through the condenser. It is helpful to know the
amount of heat rejected by the ice machine when
sizing air conditioning equipment where self-contained
air-cooled ice machines are installed.
24
Self-contained
Air-cooled
5" (127 mm)*
5" (127 mm)*
Heat of Rejection*
Air Conditioning**
1145
1450
1600
1750
2100
2200
2400
3800
Self-contained
Water-cooled
5" (127 mm)*
5" (127 mm)*
Part Number 8001119 10/19
Peak
2300
2100
2350
2600
3300
2600
3400
6000