Using The Generating Set; Starting Up The Generating Set; Turning The Generating Set Off; Control And Alarm Functions - Telair ENERGY 2510D Use And Maintenance Manual And Instructions For Installation

Table of Contents

Advertisement

The generating sets are provided with an
electronic remote control panel which allows you
to perform starting up / turning off operations as
well as to check their running conditions.
The elements making it up are (fig. 24):
1 ON/OFF switch
2 Display unit
3 High temperature indicator
4 Minimum engine oil level indicator
5 Engine start-up failed indicator
6 Generator running indicator
7 Engine oil change indicator
8 Fuel reserve indicator
9 Display changeover switch
10 Reset

7.1 Starting up the generating set

Before the first start-up check the oil level.
Set the start-up switch (fig. 24 ref. 1) to "ON"
position. The word "WAIT" will appear on the
display for 8 seconds. When these have run out,
the electronic control panel will start the first
automatic
procedure
generating set. If the engine starts up at the end
of this phase, then the "generator running"
indicator (fig. 24 ref. 6) will start to flash.
Should the engine not start up, this automatic
procedure will be repeated up to 4 times. If the
engine has not started up yet at the end of this
complete cycle, the "start-up failed" indicator ( fig.
24 ref. 5) will light up to signify that the
generating set has failed to start up.
If only the "start-up failed" indicator (fig. 12 ref. 5)
stays lit, you can repeat the start-up procedure
several times.
If the generating set has not started up at all
even after many attempts, you will have to get in
touch with the After-sales service.

7.2 Turning the generating set off

To stop the generating set, set the "ON/OFF"
switch to "OFF" position (fig. 24 ref. 1).
generating set off after disconnecting the load
Vers. 001
for
starting
up
the
Always
turn
the
Energy 2510 D
GB
7.3 Control and alarm functions (Fig. 24)
2 Display unit: when the generating set has
started up, the total running hours will be
displayed. Press the button (fig. 12 ref. 9) to
display
the
partial
generating set since the latest engine oil change.
3 High temperature indicator: this pilot lamp
will light up when the temperature of the
generating set goes over its safety value; the
engine will stop at the same time.
4 Minimum engine oil level indicator: this pilot
lamp will light up to indicate that the oil in the
engine has gone below the minimum level.
5 Engine start-up failed indicator: this pilot
lamp will light up to indicate that the generating
set has not started up, after all four attempts at
starting up have failed.
7 Engine oil change indicator: this pilot lamp
will light up when the engine has reached 100
running hours since the latest oil change. Upon
every engine oil change the After-sales service
staff must reset the Timer to make it restart from
zero.
8 Fuel reserve indicator: this pilot lamp will light
up when the fuel level has gone below its reserve
level (about 4 litres) inside the extra tank.
9 Display changeover switch: press this button
to display the running hours elapsed after the last
change of the engine oil.
when
10
Reset:
characters without logic, the panel is to be
reinitialised. Press the Reset key and, holding it
down, switch on the panel. When 4 zeroes
(0000) are shown on the display, the panel is
reinitialised.
running
hours
of
the
display
shows
the
any
15