Operation - Schwank SchwankAir 3200-Recessed Series Installation Manual

Table of Contents

Advertisement

Installation and operating instructions
General Instructions
Read these instructions carefully prior to
installation and use. Keep this manual for future
reference.
The product may only be used as set out in
the assembly and operating instructions. The
guarantee is only valid should the product be
used in the manner intended and in accordance
with the instructions.
Application area
3200-R Series is a compact air curtain for recessed
mounting. The air curtain is available without heat,
with electrical heating and with water heating.
Recommended installation height up to 11ft.
The air curtain has an integrated control system
and can also be remote controlled.
Protection class for units with electrical heating:
IP20.
Protection class for units without heating and units
with water heating: IP21.

Operation

Air is drawn in from underneath and blown
downwards shielding the door opening and
minimizing heat loss. To achieve the optimum
curtain effect the unit must extend the full width of
the opening.
The grille for directing the outlet air is adjustable
and is normally angled outwards to achieve the
best protection against incoming air.
The efficiency of the air curtain depends on the
air temperature, the pressure differencial across
the doorway and any wind load.
NOTE! Negative pressure in the building
considerably reduces the efficiency of the air
curtain. The ventilation should therefore be
balanced.
schwankgroup.com/schwankair
Mounting
The air curtain is installed horizontally with the
outlet air grille facing downwards as close to the
door as possible, concealed in the false ceiling.
The only visible part of the unit is the underside
which is level with the ceiling. The service hatch
must be accessible, nothing should prevent it
being fully opened.
The unit is ready for suspension with threaded bars
on its outside. The threaded bars can also be fixed
on the inside of the unit e.g. when mounted on a
solid suspended ceiling.
For the protection of wider doorways, several
units can be mounted in series alongside each
other. Minimum distance from outlet to floor for
electrically heated units is 70.9 in.
Mounting on threaded bars outside the unit
1. The mounting brackets are fixed to the unit
during transport. Loosen these, turn them
around and screw into place on the unit
according to fig. 1a.
2. Hang on threaded bars [M8] according to fig.
1b [accessory].
3. Adjust the height using the lower nut so that the
frame is level with the ceiling. Lock using the
upper nut.
Mounting on threaded bars inside the unit
4. The mounting brackets are fixed to the unit
during transport. Loosen them and screw them
into place inside the unit in the intended holes.
In order to mount the brackets, remove the
service hatch, outlet grille and covering plates.
5. Hang on threaded bars [M8] according to fig.
2b [accessory].
6. Adjust the height using the lower nut so that the
frame is level with the ceiling. Lock using the
upper nut.
Electrical installation
The installation, which should be preceded by
an isolator switch with a contact separation of at
least 0.12 in, should only be wired by a competent
electrician and in accordance with the latest
edition of IEE wiring regulations. The control system
is pre-installed in the air curtain.