Section 2
DNP3 data mappings
2.5
2.5.1
2.5.1.1
Table 117:

CTRL.LLN0 Local remote station off

IEC 61850 name
CTRL.LLN0
.LocRem.stVal
2.5.1.2
Table 118:

LD0.DNPGGIO1 Active parameter setting group (1)

IEC 61850 name
LD0.DNPGGIO1
.ActSG.stVal
50

Analog inputs

Table 116:
Explanations of the analog input table columns
Column name
Description
IEC 61850
Original IED data object identification. Described in the IEC 61850 format as
name
Logical Device.Logical Node and thereafter .Data Object.Data Attribute. Logical
Node is the same as the application function block name.
SA name
The signal may have a defined label that is visible, for example, in the Application
Configuration tool in PCM600.
Description
Short description of the signal. See the technical manual for more information.
Values
The value range of the original IEC 61850 data. Scaling is needed to convert
floating point data into DNP3 integer values.
S
Scaling type selected as default. Default "R" means ratio scaling. See the DNP3
communication protocol manual for details.
Arg 1, 2, 3, 4
Scaling argument values as default. When ratio scaling is selected, the four
values correspond to min value in, max value in, min value out, and max value
out. See the DNP3 communication protocol manual for details.

System functions

CTRL.LLN0 Local remote station off
SA name
Description
Off=0; Loc=1; Rem=2;
-
Station=3
LD0.DNPGGIO1 Active parameter setting group (1)
SA name
Description
-
Active setting group
Values
S
Arg 1,2,3,4
0...3
R
0,3,0,3
Values
S
Arg 1,2,3,4
1...6
R
1,6,1,6
Remote Monitoring and Control REC615
1MRS757807 B
Point List Manual