Switchgear Functions; Ctrl.cxxxxx1 Circuit Breaker (1) Cb Object And Failure Protection; Ctrl.cxxxxx2 Circuit Breaker (2) Cb Object And Failure Protection - ABB REM620 Manual

Motor protection and control dnp3 point list
Hide thumbs Also See for REM620:
Table of Contents

Advertisement

1MRS757656 A
2.3.2
2.3.2.1
Table 6:

CTRL.Cxxxxx1 Circuit breaker (1) CB object and failure protection

IEC 61850 name
CTRL.CBCILO1
.EnaCls.stVal
.EnaOpn.stVal
.ItlByPss.stVal
CTRL.CBCSWI1
.Pos.stSeld
CTRL.CBXCBR1
.BlkCls.stVal
.BlkOpn.stVal
CTRL.CCBRBRF1
.OpEx.general
.OpIn.general
.Str.general
2.3.2.2
Table 7:

CTRL.Cxxxxx2 Circuit breaker (2) CB object and failure protection

IEC 61850 name
CTRL.CBCILO2
.EnaCls.stVal
.EnaOpn.stVal
.ItlByPss.stVal
CTRL.CBCSWI2
.Pos.stSeld
CTRL.CBXCBR2
.BlkCls.stVal
.BlkOpn.stVal
CTRL.CCBRBRF2
.OpEx.general
.OpIn.general
.Str.general
REM620
Point List Manual

Switchgear functions

CTRL.Cxxxxx1 Circuit breaker (1) CB object and failure protection
SA name
ENA_CLOSE
ENA_OPEN
ITL_BYPASS
SELECTED
BLK_CLOSE
BLK_OPEN
TRBU
TRRET
CB_FAULT_AL
CTRL.Cxxxxx2 Circuit breaker (2) CB object and failure protection
SA name
ENA_CLOSE
ENA_OPEN
ITL_BYPASS
SELECTED
BLK_CLOSE
BLK_OPEN
TRBU
TRRET
CB_FAULT_AL
Description
Close enabled
Open enabled
Interlocking bypass
CB selected
Close blocked
Open blocked
Failure ext.trip
Operate, re-trip
Start, timer running
Description
Close enabled
Open enabled
Interlocking bypass
CB selected
Close blocked
Open blocked
Failure ext.trip
Operate, re-trip
Start, timer running
Section 2
DNP3 data mappings
Values
1=Enabled
1=Enabled
1=Bypassed
1=Selected
1=Blocked
1=Blocked
1=Failure
1=Operate
1=Start
Values
1=Enabled
1=Enabled
1=Bypassed
1=Selected
1=Blocked
1=Blocked
1=Failure
1=Operate
1=Start
19