PARAMETER TABLE
FOLD
PAR.
DESCRIPTION
At1
PULSE OUTPUT
At1
U01
PWM period.
At1
U02
maximum valve opening %.
valve actuation % after blackout for time set by OtF.
At1
U03
NOTE. Calculated automatically but modifiable for first startup.
valve actuation % after defrost for time set by OtF.
At1
U04
NOTE. Calculated automatically but modifiable for first startup. If %=0 is defined by U03
Valve operating time at maximum opening for alarm signal. If the valve is at maximum opening (see
At1
U05
U02) for a time longer than U05, the alarm is activated
At1
U06
minimum valve useful opening %.
At1
U07
maximum valve useful opening %.
CnF
CONFIGURATION
CnF
H00
Overheating probe configuration. diS = disabled; ntC= NTC; 420= 4...20mA
Saturation probe configuration. diS = disabled; ntC= NTC; 420= 4...20mA; rA=ratiometric trans-
CnF
H01
ducer 30bar; LAn = remote (shared pressure transducer). See Application with multiple V800 drivers
/ ID985/V controllers.
CnF
H03
Lower current limit for input.
CnF
H04
Upper current limit for input.
29 - EN
RANGE
DEF.
U.o.M.
3...10
6
sec
0...100
100
number
0...100
0
number
0...100
0
number
0...255
60
min
0...100
0
number
0...100
100
number
diS/ntC/420
ntC
number
diS/ntc/420/
420
number
rA/LAn
-14.5...1000.0
-0.5
bar/PSI
-14.5...1000.0
7.0
bar/PSI
VAL
V800