Dipswitch Protocol Selection - Eliwell V800 Series Manual

Driver for electronic expansion valve
Table of Contents

Advertisement

Available languages

Available languages

(To configure the device for this purpose, open the folder identified by the 'Add' label and use parameters:
• PtS to select the TelevisSystem / Modbus RTU protocol
• TelevisSystem: dEA and FAA.
• Modbus RTU: dEA / FAA / PtY for the parity / Ptb for the baud rate.
NOTE: the connection serial port between the devices is powered.
Dip Switch Protocol Selection
Protocol Selection
Protocol
LAN
Televis/Modbus
V800
LED C
3
yellow
OFF
OFF
ON
ON
LAN
DipSwitch3=OFF only for use with IWK/V
NOTE: TTL port shall NOT be connected to any
device
Televis/Modbus
DipSwitch3=ON per Televis/Modbus supervision or use
with DMI/CC
NOTA: IWK/V shall NOT be connected
20 - EN