• Analogue input setting display
To know the configuration of the analog input use the command:
ADCINFO
• Activation of outputs in alarm condition
The OUTALARM command determines the behaviour of the relay outputs following alarm
originating from digital inputs or analogue input.
OUTALARM [output number][output status][cause of alarm][reset alarm mode]
[output number] 
[output status] 
[[cause of alarm] 
[alarm reset mode]  MAN manual, AUTO at the end of the alarm condition
Examples:
OUTALARM 2 ON DIG1 AUTO
OUTALARM 2 OFF DIG2 MAN
OUTALARM 1 ON MIN AUTO
OUTALARM 2 ON MAX AUTO
OUTALARM 2 DISABLE
Example: OUTALARM 1 OFF POWERF AUTO
1 or 2
ON, OFF or DISABLE
DIG1, DIG2, MIN, MAX, LOWBAT, POWERF
 in the case of digital alarm 1 output 2 becomes
ON and changes status at the end of the alarm
condition
 in the case of digital alarm 2 output 2 becomes
OFF and remains in such status
 in the case of minimum alarm for the analogue
input, output 1 becomes ON and changes
status at the end of the alarm condition
 in the case of maximum alarm for the analogue
input, output 2 becomes ON and changes
status at the end of the alarm condition
 function disabled