Na-protection according to vde-ar-n 4105, in-plant power generators on the low voltage grid;
for use in in-plant power generators on the medium voltage grid according to bdew;with selectable vector shift detection;with selectable rate of change of freque (46 pages)
Summary of Contents for ZIEHL MS220VA
Page 1
ZIEHL industrie – elektronik GmbH + Co KG Daimlerstraße 13, D – 74523 Schwäbisch Hall + 49 791 504-0, info@ziehl.de, www.ziehl.de Temperature Relays and MINIKA® Mains Monitoring Digital Panelmeters MINIPAN® Switching Relays and Controls Measuring Transducers Grid- and Plant Protection...
1 Application and brief description Ziehl PTC thermistor relays protect motors, transformers, machines and equipment against thermal overload. These are according to DIN EN 60947-8 and are thus exchangeable. Used in conjunction with respective PTC thermistors they provide a reliable temperature protection in the temperature range 60 °C up to 180 °C.
TNF + 15 K TNF + 5 K TNF – 5 K 3 PTC thermistors in series TNF + 5 K TNF – 20 K 6 PTC thermistors in series MS220VA and MSR220VA 1166 0732_GB Seite 4 / 12 www.ziehl.de...
7 Function diagram MS220VA (automatic reset) A1/A2 3650 ¦ 1500 ¦ T1/T2 LED ON LED ALARM MSR220VA (reclosing lock) A1/A2 3650 ¦ 1500 ¦ T1/T2 LED ON LED ALARM (Reset) MS220VA and MSR220VA 1166 0732_GB Seite 5 / 12 www.ziehl.de...
With no PTC sensor connected the relay must release. The voltage at terminals T1-T2 must be approx. 8 V. In case of any other malfunctions, replace device. Please add a description of the occurred malfunction when sending back for repair. MS220VA and MSR220VA 1166 0732_GB Seite 6 / 12 www.ziehl.de...
Rated ambient temperature range -20 ... +55° C EMC - Immunity EN 61000-6-2 EMC - Emission EN 61000-6-3 2…13.2 Hz ± 1 mm Vibration resistance EN 60068-2-6 13.2 ... 100 Hz 1 g MS220VA and MSR220VA 1166 0732_GB Seite 7 / 12 www.ziehl.de...
11 Design V2 Dimensions in mm 16,5 Option Bottom Bolt Seal mounting link Front plate element Characteristic for bottom Extensible bolt for wall fastening with screws. Bolt bore Ø 4.2 mm. MS220VA and MSR220VA 1166 0732_GB Seite 8 / 12 www.ziehl.de...
5 years 10 years interval T1 MS220VA PFDavg 1.78E-03 5.35E-03 8.91E-03 1.78E-02 MSR220VA PFDavg 1.87E-03 5.60E-03 9.33E-03 1.87E-02 Observe proof test interval according EN 60079-17 for electrical equipment ≤ 3 years. MS220VA and MSR220VA 1166 0732_GB Seite 9 / 12 www.ziehl.de...
(see connection diagram) so the supervised motor/machine does not start again independently. Attention! Safety circuits according to EN 60204/EN 62061. The tripping devices must not be used alone for functions, where an automatic Restart must be prevented. MS220VA and MSR220VA 1166 0732_GB Seite 11 / 12 www.ziehl.de...
EN 60079-17 is to be observed. You’ll find this and other user manuals in the internet under www.ziehl.com MS220VA and MSR220VA 1166 0732_GB Seite 12 / 12 www.ziehl.de...