While connecting the sensor:
"1" — norm;
"0" — alarm.
Attention! The corresponding IO-line must be switched to the "input" mode in the device settings.
The sensor is supplied with a 2 m connection cable. You can extend the length of the cable
4m, which are connected in series into each other, or independently using any wire with a cross section of at least
2
0.4
mm
. The maximum permissible loop length is 100 meters.
The sensor has two connectors on different sides 6p6c for connecting to the monitoring device and 4p4c for
connecting to the sensitive cable.