5 Application guidelines
▪ Connection and setup:
▪ Connect the second power meter to X5M/9 and X5M/10.
▪ In the software the power consumption data of both meters is
added so you do NOT have to set which meter covers which
power consumption. You only need to set the number of pulses
of each power meter.
▪ See
"5.4.4  Preferential kWh rate power supply"  on page  14
an example with two power meters.
5.4.4

Preferential kWh rate power supply

General rule
▪ Power meter 1: Measures the outdoor unit.
▪ Power meter  2: Measures the rest (i.e. indoor unit and backup
heater).
Setup
▪ Connect power meter 1 to X5M/7 and X5M/8.
▪ Connect power meter 2 to X5M/9 and X5M/10.
Power meter types
▪ Power meter 1: Single- or three-phase power meter according to
the power supply of the outdoor unit.
▪ Power meter 2: Use a single-phase power meter.
5.5
Setting up the power consumption
control
▪ The power consumption control:
▪ Is only applicable for EHVZ04+08.
▪ Allows you to limit the power consumption of the entire system
(sum of outdoor unit, indoor unit and backup heater).
▪ Configuration: Set the power limitation level and how it has to
be achieved via the user interface.
▪ The power limitation level can be expressed as:
▪ Maximum running current (in A)
▪ Maximum power input (in kW)
▪ The power limitation level can be activated:
▪ Permanently
▪ By digital inputs
5.5.1

Permanent power limitation

Permanent power limitation is useful to assure a maximum power or
current input of the system. In some countries, legislation limits the
maximum power consumption for space heating and DHW
production.
P
i
a
DI
b
t
P
Power input
i
t
Time
DI
Digital input (power limitation level)
a
Power limitation active
b
Actual power input
Setup and configuration
▪ No additional equipment needed.
Installer reference guide
14
▪ Set the power consumption control settings in [A.6.3.1] via the
user
interface
(for
"8 Configuration" on
▪ Select full time limitation mode
▪ Select the type of limitation (power in kW or current in A)
▪ Set the desired power limitation level
for
NOTICE
Mind the following guidelines when selecting the desired
power limitation level:
▪ Set a minimum power consumption of ±3.6  kW to
guarantee defrost operation. Otherwise, if defrosting is
interrupted several times, the heat exchanger will
freeze up.
▪ Set a minimum power consumption of ±3  kW to
guarantee space heating and DHW production by
allowing the backup heater step 1.
5.5.2
Power limitation activated by digital
inputs
Power limitation is also useful in combination with an energy
management system.
The power or current of the entire Daikin system is limited
dynamically by digital inputs (maximum four steps). Each power
limitation level is set via the user interface by limiting one of the
following:
▪ Current (in A)
▪ Power input (in kW)
The energy management system (field supply) decides the activation
of a certain power limitation level. Example: To limit the maximum
power of the entire house (lighting, domestic appliances, space
heating...).
C
a
5
4
3
A8P
2
1
b
A
B
A
Outdoor unit
B
Indoor unit
C
Energy management system
a
Power limitation activation (4 digital inputs)
b
Backup heater
P
i
a
DI1
DI3
DI4
P
Power input
i
t
Time
DI
Digital inputs (power limitation levels)
a
Power limitation active
b
Actual power input
Setup
▪ Demand PCB (option EKRP1AHTA) needed.
the
description
of
all
settings,
page 39):
b
t
ERHQ+ERLQ011~016 + EHVZ16S18CB
Daikin Altherma – Low temperature split
4P401677-1 – 2015.02
see