5 Application guidelines
Selecting the desired temperature for the DHW tank consists of:
1
Determining the DHW consumption (equivalent hot water
volume at 40°C).
2
Determining the desired temperature for the DHW tank.
Energy saving tips
▪ If the DHW consumption differs from day to day, you can program
a weekly schedule with different desired DHW tank temperatures
for each day.
▪ The lower the desired DHW tank temperature, the more cost
effective. By selecting a larger DHW tank, you can lower the
desired DHW tank temperature.
▪ The heat pump itself can produce domestic hot water of maximum
55°C (50°C if outdoor temperature is low). The electrical
resistance integrated in the heat  pump can increase this
temperature. However, this consumes more energy. Daikin
recommends to set the desired DHW tank temperature below
55°C to avoid using the backup heater.
▪ The higher the outdoor temperature, the better the performance of
the heat pump.
▪ If energy prices are the same during the day and the night,
Daikin recommends to heat up the DHW tank during the day.
▪ If energy prices are lower during the night, Daikin recommends
to heat up the DHW tank during the night.
▪ When the heat pump produces domestic hot water, it cannot heat
up a space. When you need domestic hot water and space
heating at the same, Daikin recommends to produce the domestic
hot water during the night when there is lower space heating
demand.
Determining the DHW consumption
Answer the following questions and calculate the DHW consumption
(equivalent hot water volume at 40°C) using the typical water
volumes:
Question
How many showers are needed
per day?
How many baths are needed per
day?
How much water is needed at the
kitchen sink per day?
Are there any other domestic hot
water needs?
Example: If the DHW consumption of a family (4 persons) per day is
as follows:
▪ 3 showers
▪ 1 bath
▪ 3 sink volumes
Then the DHW consumption = (3×100 l)+(1×150 l)+(3×10 l)=480 l
Determining the volume and desired temperature for the DHW
tank
Formula
V
=V
+V
×(T
−40)/(40−T
)
1
2
2
2
1
V
DHW consumption (equivalent hot water volume at 40°C)
1
V
Required DHW tank volume if only heated once
2
T
DHW tank temperature
2
T
Cold water temperature
1
Installer reference guide
12
Typical water volume
1 shower = 10 min×10 l/min =
100 l
1 bath = 150 l
1 sink = 2 min×5 l/min = 10 l
Example
If:
▪ V
=180 l
2
▪ T
=54°C
2
▪ T
=15°C
1
Then V
=280 l
1
5.3.3
Setup and configuration – DHW tank
▪ For large DHW consumptions, you can heat up the DHW tank
several times during the day.
▪ To heat up the DHW tank to the desired DHW tank temperature,
you can use the following energy sources:
▪ Thermodynamic cycle of the heat pump
▪ Electrical backup heater
▪ For more information about optimizing the energy consumption for
producing domestic hot water, see
5.3.4

DHW pump for instant hot water

Setup
h
c
a
i
f
b
g
a
Indoor unit
b
DHW tank
c
DHW pump (field supply)
f
Shower (field supply)
g
Cold water
h
Domestic hot water OUT
i
Recirculation connection
▪ By connecting a DHW pump, instant hot water can be available at
the tap.
▪ The DHW pump and the installation are field supply and the
responsibility of the installer.
▪ For
more
information
about
connection: see
"7 Installation" on
Configuration
▪ For more information, see
"8 Configuration" on
▪ You can program a schedule to control the DHW pump via the
user interface. For more information, see the user reference
guide.
5.3.5

DHW pump for disinfection

Setup
h
c
a
i
d
f
b
e
g
a
Indoor unit
b
DHW tank
c
DHW pump (field supply)
d
Heater element (field supply)
e
Non‑return valve (field supply)
f
Shower (field supply)
g
Cold water
h
Domestic hot water OUT
i
Recirculation connection
▪ The DHW pump is field-supplied and its installation is the
responsibility of the installer.
▪ The temperature of the DHW tank can be set to maximum 60°C. If
applicable legislation requires higher temperature for disinfection,
you can connect a DHW pump and heater element as shown
above.
▪ If applicable legislation requires disinfection of the water piping
until the tapping point, you can connect a DHW pump and heater
element (if needed) as shown above.
▪ To ensure a complete disinfection, you have to open the tapping
point.
"8 Configuration" on
page 39.
connecting
the
recirculation
page 21.
page 39.
ERHQ+ERLQ011~016 + EHVZ16S18CB