Installer Setting -E.S.P.

This is the function that decides the strength of the wind for each wind level and because this
function is to make the installation easier.
- If you set ESP incorrectly, the air conditioner may malfunction.
- This setting must be carried out by a certificated-technician.
FAN
SPEED
TEMP
- Precaution shall be taken not to alter the E.S.P value corresponded to each air flow section.
- E.S.P value can be varied according to the products.
- In the case of going to the next air flow rate stage by pressing the fan-speed button during the
setup of the E.S.P value, the E.S.P value of previous air flow rate will be maintained by remem-
bering the E.S.P value prior to the shift.
1
2
3
OPER
MODE
4
5
OPTIONAL OPERATION
When pressing the
button simultaneously for more than 3
seconds, the system will be entered into
the installer setting mode.
- After entering into the installer setting
mode, select the E.S.P code value by
OPER
pressing the
button.
MODE
* E.S.P code value : 03
Select the desired air flow rate with
FAN
the
button. Whenever pressing
SPEED
the
FAN
button, [Lo→Med→Hi] will be
SPEED
indicated.
Select the desired air flow rate value with
the temperature up(▲), down(▼) button.
* E.S.P value range : 0~255
- E.S.P value will be indicated at the lower
right section of the display window.
When pressing the
established E.S.P value will be set up.
When pressing the
button simultaneously for more than 3
seconds after the setting has been
completed, the setting mode will be
released.
- If there isn't any button input for more
than 25 seconds, the installer setting
mode will also be released.