6. External view of P.C. board assembly
7. Address setup
In addition to set up the central control address, it is necessary to change the indoor unit number.
(Line/Indoor/Group address). For details, refer to 1:1 model connection interface Installation Manual.

8-3. How to Set up Central Control Address Number

When connecting the indoor unit to the central control remote controller using 1:1 model connection interface,
it is necessary to set up the central control address number.
• The central control address number is displayed as the line No. of the central control remote controller.
How to set up from indoor unit side by remote controller
<Procedure> Perform setup while the unit stops.
1
VENT
TEST
Push
+
buttons for 4 seconds or more.
When group control is executed, first the unit No.
control are selected. In this time, fans of all the selected indoor units are turned on. (Fig. 1)
(Keep
displayed status without pushing
In case of individual remote controller which is not group-controlled, Line address and Indoor unit address
are displayed.
2
Using temperature setup
3
Using timer time
The setup data is shown in the table below (Table 1).
4
SET
Push
button. (OK if display goes on.)
• To change the item to be set up, return to Procedure
5
TEST
Push
button.
The status returns to usual stop status.
(Table 1)
SET DATA
Central control address No.
0001
0002
0003
:
0064
0099
Unset (Setup at shipment from factory)
Terminator (SW01)
TEMP.
buttons, specify CODE No.
TIME
buttons, select the SET DATA.
1
2
3
:
64
85
is displayed and all the indoor units in the group
button.)
UNIT LOUVER
03 03 03 03 03
2
.
2
1
FILTER
RESET
5
- 75 -
FILE NO. SVM-18039
52
.
(Fig.1)
CODE No.
SET DATA
SETTING
UNIT No.
R.C. No.
TEMP.
ON / OFF
TIMER SET
FAN
MODE
TIME
SAVE
VENT
TEST
SET
CL
SWING/FIX
UNIT LOUVER
3
1
4