Toshiba RAV-RM1601BTP Series Service Manual page 66

Table of Contents

Advertisement

DN
Item
01
Filter sign lighting time}
02
Dirty state of filter
03
Central control address
06
Heating suction temp shift
0F
Cooling only
10
Type
11
Indoor unit capacity
12
Line address
13
Indoor unit address
14
Group address
19
Louver type
(Air direction adjustment)
∗ None for concealed duct
1E
Temp difference of
automatic cooling/heating
mode selection COOL →
HEAT, HEAT →COOL
28
Auto restart after power
failure
2A
Option
2b
Thermo output selection
(T10
)
2E
Option
30
Option
31
Option
32
Sensor selection
33
Temperature indication
40
Option
5d
High ceiling selection
(External static pressure
selection)
Item No. (DN) table (Selection of function)
Description
0000 : None
0002 : 2500H (4-Way/Duct/Ceiling Type)
0000 : Standard
0001 : No.1 unit
to
0099 : Unfixed
0000 : No shift
0002 : +2°C
to
0000 : Heat pump
0004 : Concealed duct type
0014 : Compact 4-way cassette type
0000 : Unfixed
0007 : 45 type
0012 : 80 type
0017 : 140 type
0001 : No.1 unit
to
0001 : No.1 unit
to
0000 : Individual
0002 : Follower of group
0000 : No louver
0002 : 1-way
0004 : 4-way
0000 : 0 deg to
(For setup temperature, reversal of COOL/HEAT by ± (Data value)/2)
0000 : None
0000 : Indoor thermo ON
0001 : Output of outdoor comp-ON receiving
0000 : Body TA sensor0001 : Remote controller sensor
0000 : °C (celsius)
<Concealed Duct type>
Set data
0000
40 Pa
External static
pressure
The list above is when SW501-1 and SW501-2 is OFF.
- 66 -
0001 : High degree of dirt
(Half of standard time)
0064 : No.64 unit
0001 : +1°C
0010 : –10°C
(Up to recommendation + 6)
0001 : Cooling only
(No display of [AUTO] [HEAT])
0007 : Ceiling type
0006 : 40 type
0009 : 56 type
0015 : 110 type
0018 : 160 type
0030 : No.30 unit
0064 : No.64 unit
0001 : Master of group
0001 : Swing only
0003 : 2-way
0010 : 10 deg
0001 : Auto restart
0001 : °F (Fahrenheit)
0001
0002
0003
30 Pa
65 Pa
50 Pa
To 3HP
4 to 6HP
(Factory
(Factory
default)
default)
FILE NO. SVM-18039
At shipment
0002 : 2500H
0000 : Standard
0099 : Unfixed
0002 : +2°C
0000 : Heat pump
According to model type
According to capacity type
0099 : Unfixed
0099 : Unfixed
0099 : Unfixed
According to model type
0003 : 3 deg (Ts±1.5)
0000 : None
0002 : Default
0000: Thermo. ON
0000 : Default
0000 : Default
0000 : Default
0000 : Body sensor
0000 : °C
0003 : Default
According to capacity type
0004
0005
0006
80 Pa
100 Pa
120 Pa

Hide quick links: