Wiring Directions; Connecting Wires - LEGRAND Wattstopper UT-300-1 Manual

Ultrasonic low voltage occupancy sensor with manual on feature, light level and isolated relay
Hide thumbs Also See for Wattstopper UT-300-1:
Table of Contents

Advertisement

Available languages

Available languages

Each Wattstopper BZ series power pack can supply power for 5 UT-300
sensors. When using more sensors than this, multiple power packs are
required.
Refer to the wiring diagram for the following procedures:
Connect the low voltage:
• RED wire (+24VDC) from power pack to the +24V terminal on the sensor.
• BLACK wire (Return) from power pack to Common terminal on the sensor.
• BLUE wire from power pack to Control Out terminal on sensor.
To add a manual switch such as the LVS-1 Momentary Toggle Switch, or
RS2-3 Low Voltage Momentary Switch to the above applications–connect:
• Wire from one side of switch to +24V terminal on sensor.
• Wire from other side of switch to Man Switch terminal on sensor.
Wiring the Isolated Relay: (The Isolated Relay is rated for 1A@30VAC/VDC)
Connect the wires necessary to the application that requires this output:
• Relay Common (must be used for proper operation).
• N.O. (Normally Open)–Closed when occupancy is detected.
• N.C. (Normally Closed)–Open when occupancy is detected.
• Care should be taken to separate high voltage power from low voltage (Class 2) control wiring.
• All connections to sensor are low voltage, Class 2.
Standard wiring with local off switch
Line
Neutral
Power Pack
Low Voltage
Class 2
Black
Common
Red
+24V
Ceiling
Depluggable
Terminal
Spring Clips (2)
Rear Housing
Front Cover
UT-300
Directly to Ceiling
1. Attach the plastic spring clips to the edge of the sensor in the slots provided.
2. Cut a 3.5" to 4" round hole in the acoustic ceiling tile at the mounting location. A 3.5"
hole is recommended for a secure fit.
3. Pull the low voltage wire from the power pack to the sensor through the hole.
4. Connect the low voltage wires to the appropriate terminals on the sensor.
5. Push the sensor up through the hole until the Spring Clips hold the sensor securely in
place.
6. Snap the front cover onto the sensor.
Feed Through
Load #1
Load #2
(Optional)
Line
Voltage
Blue
Control Out
#1
Line Voltage
Switches
MOUNTING THE SENSOR

WIRING DIRECTIONS

CONNECTING WIRES

Manual-On wiring with low voltage momentary switch
Ceiling
Depluggable
Terminal
Spring Clips (2)
#2
Rear Housing
Front Cover
2
WARNING: TURN THE POWER OFF AT THE
CIRCUIT BREAKER BEFORE WIRING.
Line
Neutral
Power Pack
Low Voltage
Class 2
Red
Blue
+24V
Control Out
Black
Common
Man. Switch
UT-300
03620r2
UT-300
Relay Com.
V3
Ultrasonic
N.O.
Occupancy Sensor
N.C.
40kHz Ultrasonic
+24VDC/VAC
Connect to WattStopper
Class 2 Power Packs
For Indoor Use Only
Control Out.
U.S.Patents:
Man. Switch
LISTED
5,640,113
88T9
Patent Pending
Appliance
+24V
Control
Common
Wiring
terminals
Feed Through
Load
Line Voltage
+24V
Man.Switch
Jumper
Back
of
LVS-1
LVS-1
For low voltage
momentary switch, set
DIP switch #6 ON
Ceiling Mount