Top Vent - Horizontal Termination
One Elbow
CAUTION: The SLP-HRC-SS termination caps are
not approved for use with these models. May lead to
elevated glass temperature that may cause tempered
glass breakage.
Note: Use SLP Series
components only.
Note: There MUST be a 25% reduction
in total H when using SLP-FLEX Series
(6-5/8 inch) vent except when using
the simple up and out installation. See
Figure 4.10.
Figure 4.12
Hearth & Home Technologies • DVLINEAR36 Installation Manual • 2569-980 Rev. E • 11/20
V Minimum
90° Elbow
1 ft.
305 mm
2 ft.
610 mm
3 ft.
914 mm
4 ft.
1.2 m
5 ft.
1.5 m
H MAX. =14 ft. (4.3 m)
V + H MAX. = 40 ft. (12.2 m)
H
1
H
Maximum
1
1 ft.
305 mm
2 ft.
610 mm
3 ft.
914 mm
5 ft.
1.5 m
7 ft.
2.1 m
14 ft.
4.3 m
V
1
25