Installation - LEGRAND WattStopper DW-100-24-LA Installation Instructions Manual

Dual technology low voltage wall switch occupancy sensor
Table of Contents

Advertisement

INSTALLATION

TURN THE POWER OFF AT THE CIRCUIT BREAKER BEFORE
INSTALLING THE SENSOR OR WORKING ON THE LOAD.
1. Install the power pack according to its instructions.
2. Connect the power pack wires to the sensor as follows:
RED wire (+24VDC) to the +24V IN terminal on the sensor.
BLACK wire (Return) to common (COMM.) terminal on the sensor.
BLUE wire to control output (CTRL. OUT) terminal on the sensor.
3. Wire the Isolated Relay. The Isolated Relay is rated for 1A @ 30VAC/VDC.
Connect the wires necessary to the application that requires this output:
• Normally Closed (N.C.) - Open when occupancy is detected.
• Relay Common (must be used for proper operation)
• Normally Open (N.O.) - Closed when occupancy is detected.
The bottom terminal on the sensor is not used.
4. Turn the power on.
5. Test and adjust the sensor if necessary.
6. Install industry standard decorator wall switch cover plate (not
included).
White
Neutral
Black
Hot
Visit our website for FAQs: www.wattstopper.com
WARNING
White (Neutral)
Red (Line)
Power
Pack
+24 VDC
Common
Control Outputs
Normally closed contact
Common
Normally open contact
Not used
D-100-24 Wiring
Lighting
Load
Red
(Load)
Isolated Relay Outputs