Installation; Lens Options - LEGRAND Wattstopper FSP-211-CFG Installation Instructions Manual

High/low/off pir fixture integrated outdoor sensor
Table of Contents

Advertisement

Available languages

Available languages

INSTALLATION

1. Determine an appropriate mounting location inside the light fixture
minimizing the electric light contribution to the sensor's photocell.
Allow a minimum distance of 0.2" (5.1mm) from the wiring end of
the sensor to the wall of the fixture.
2. Drill a hole 1.30" (33.0mm) in diameter through the sheet metal in
the bottom of the fixture.
3. Add the rubber gasket to the threaded collar, and install the sensor
face down, parallel to the mounting surface. Ensure the rubber
gasket touches the inside surface of the fixture. Install the plastic
nut (or optional collar) securely against the fixture to a torque of
25–30 in-lbs to ensure IP rating is maintained.
4. Align the locking features between the sensor and lens module and
push the lens module forward until the o-ring seals firmly. Turn the
lens module clockwise to ensure it locks in place.
5. Connect wires as shown in wiring diagram.
6. Restore power from the circuit breaker.
NOTE: An optional collar can be installed in place of the tightening nut.
See the Ordering Information table on page 4 for details.
Several lenses are available for use with the FSP-211. Lenses give coverage at mounting heights between 8' – 40' for applications such
as offices, warehouses, and outdoor use. Density and range of the coverage is determined by the type of lens and mounting height.
A lens with shroud option is also available. The shroud blocks light coming from the fixture, to prevent interference with the photocell
function of the sensor. Lens modules are IP-66 rated when combined with an FSP-211 sensor mounted to an outdoor-rated fixture. See
the FSP-Lx Lens Coverage Guide for more information.
Non-Dimming
Driver
OUTDOORS—USE AT THE EXPOSED SENSOR COLLAR PART ONLY WHEN INSTALLED AT THE SPECIFIC LOCATION PER
NEUTRAL
LOAD
16-18 AWG Solid CU
Wire Only
FSP-211
FSP-211
v2
High/Low PIR
Occupancy Sensor
230-240V~, 50/60 Hz
300W max ballast
5E4, 40T75
LISTED
Appliance
Control
88T9
E101196
120V/277V, 50/60 Hz: UL/cUL
800W/1200W Max Tungsten,
Ballasts or LED Driver
1/6 HP
www.legrand.us/wattstopper
18-20 AWG Solid CU Wire Only
INSTALLATION INSTRUCTIONS WITH A LISTED OUTDOOR ENCLOSURE.
WARNING: TURN THE POWER OFF AT THE
Inside Fixture
Wall
Tightening Nut
(or Optional Collar)
NOTE: The Outside Fixture Wall thickness should be no

LENS OPTIONS

WIRING
NOTE: Per UL, the 0-10V negative
dimming wire color has been changed
from gray to pink.
2
CIRCUIT BREAKER BEFORE WIRING.
FSP-211
Rubber
Gasket
Outside
Tightening Nut
Fixture Wall
(or Optional Collar)
greater than 0.125" (3.18mm) for optimal sensor
mounting and security.
NEUTRAL
LOAD
Dimming
Driver
PINK (-)
PURPLE (+)
Rubber
Gasket
Fixture
Wall
Lens Assembly
16-18 AWG Solid CU
Wire Only
FSP-211
FSP-211
v2
High/Low PIR
Occupancy Sensor
230-240V~, 50/60 Hz
300W max ballast
5E4, 40T75
LISTED
Appliance
Control
88T9
E101196
120V/277V, 50/60 Hz: UL/cUL
800W/1200W Max Tungsten,
Ballasts or LED Driver
1/6 HP
www.legrand.us/wattstopper
18-20 AWG Solid CU Wire Only