Daikin ERGA08DAV3 Installer's Reference Manual page 97

Hide thumbs Also See for ERGA08DAV3:
Table of Contents

Advertisement

Field settings table
Breadcrumb
Field code
Setting name
9.3.7
[5-01]
Equilibrium temperature
9.3.8
[4-00]
Operation
└─ Booster heater
9.4.1
[6-02]
Capacity
9.4.3
[8-03]
BSH eco timer
9.4.4
[4-03]
Operation
Installer settings
9.5
[4-06]
Emergency
└─ Balancing
9.6.1
[5-02]
Space heating priority
9.6.2
[5-03]
Priority temperature
9.6.3
[5-04]
Offset BSH setpoint
9.6.4
[8-02]
Anti-recycle timer
9.6.5
[8-00]
Minimum running timer
9.6.6
[8-01]
Maximum running timer
9.6.7
[8-04]
Additional timer
Installer settings
9.7
[4-04]
Water pipe freeze prevention
└─ Benefit kWh power supply
9.8.1
[D-01]
Benefit kWh power supply
9.8.2
[D-00]
Allow heater
9.8.3
[D-05]
Allow pump
└─ Power consumption control
9.9.1
[4-08]
Power consumption control
9.9.2
[4-09]
Type
9.9.3
[5-05]
Limit
9.9.4
[5-05]
Limit 1
9.9.5
[5-06]
Limit 2
9.9.6
[5-07]
Limit 3
9.9.7
[5-08]
Limit 4
9.9.8
[5-09]
Limit
9.9.9
[5-09]
Limit 1
9.9.A
[5-0A]
Limit 2
9.9.B
[5-0B]
Limit 3
9.9.C
[5-0C]
Limit 4
9.9.D
[4-01]
Priority heater
└─ Energy metering
9.A.1
[D-08]
Electricity meter 1
9.A.2
[D-09]
Electricity meter 2
└─ Sensors
9.B.1
[C-08]
External sensor
9.B.2
[2-0B]
Ext. amb. sensor offset
9.B.3
[1-0A]
Averaging time
└─ Bivalent
(*1) *3V_
(*2) *6V_
(*3) *9W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
(#) Setting is not applicable for this unit.
Range, step
Default value
-15~35°C, step: 1°C
0°C
0: Disabled
1: Enabled
2: Only DHW
0~10kW, step: 0,2kW
0kW
20~95 min, step: 5 min
50 min
0: Restricted
1: Allowed
2: Overlap
3: Compressor off
4: Legionella only
0: Manual
1: Automatic
0: Disabled
1: Enabled
-15~35°C, step: 1°C
0°C
0~20°C, step: 1°C
10°C
0~10 hour, step: 0,5 hour
0,5 hour
0~20 min, step 1 min
1 min
5~95 min, step: 5 min
30 min
0~95 min, step: 5 min
95 min
0: Intermittent
1: Continuous
2: Off
0: No
1: Active open
2: Active closed
3: Safety thermostat
0: None
1: BSH only
2: BUH only
3: All heaters
0: Forced off
1: As normal
0: No limitation
1: Continuous
2: Digital inputs
0: Current
1: Power
0~50 A, step: 1 A
50 A
0~50 A, step: 1 A
50 A
0~50 A, step: 1 A
50 A
0~50 A, step: 1 A
50 A
0~50 A, step: 1 A
50 A
0~20 kW, step: 0,5 kW
20 kW
0~20 kW, step: 0,5 kW
20 kW
0~20 kW, step: 0,5 kW
20 kW
0~20 kW, step: 0,5 kW
20 kW
0~20 kW, step: 0,5 kW
20 kW
0: None
1: BSH
2: BUH
0: No
1: 0,1 pulse/kWh
2: 1 pulse/kWh
3: 10 pulse/kWh
4: 100 pulse/kWh
5: 1000 pulse/kWh
0: No
1: 0,1 pulse/kWh
2: 1 pulse/kWh
3: 10 pulse/kWh
4: 100 pulse/kWh
5: 1000 pulse/kWh
0: No
1: Outdoor sensor
2: Room sensor
-5~5°C, step: 0,5°C
0°C
0: No averaging
1: 12 hours
2: 24 hours
3: 48 hours
4: 72 hours
5/9
Installer setting at variance with
default value
Date
Value
4P495259-1B - 2019.06