13 Disposal
L N PWR
1
2 3
L
N
4 Set DIP switches SW5 and SW6 to OFF.
5 Set DIP switch SW2 to COOL.
6 Reattach the service PCB cover.
7 Turn the power back ON. Proceed with the next step within 3
minutes after restarting.
8 To start forced cooling, press the forced cooling operation
switch SW1.
9 To stop forced cooling, press the forced cooling operation
switch SW1 again.
10 Turn OFF the power, remove the switch box cover and service
PCB cover and set the DIP switches SW5, SW6 and SW2 back
to their original position.
11 Reattach the service PCB cover and switch box cover and turn
the power back ON.
NOTICE
Take care that while running forced cooling operation, the
water
temperature
remains
temperature read out of the indoor unit). You can achieve
this, for example, by activating all fans of the fan coil units.
Installer reference guide
84
E
A
SW4
D
C
B
1
A
SW6
2
1
2
4
SW5
3
3
2
1
4
COOL
HEAT
SW2
5
SW3
SW1
higher
than
5°C
(see
ERGA04~08DAV3(A) + EHVZ04+08S18+23DA +
EHVZ04+08S18+23DJ
Daikin Altherma 3 R F
4P495249-1B – 2019.06