Specifications
CPU Unit and Expansion I/O Unit Output Specifications
Item
Output type
Max. switching capacity
Min. switching capacity
Service life of relay
ON delay
OFF delay
Circuit configuration
Caution
!

2-1-4 Communications Adapter Specifications

RS-232C Adapter Specifications
Item
Function
Insulation
Power supply
Power consumption
Baud rate
Transmission distance
Vibration resistance
Shock resistance
Ambient temperature
Humidity
Atmosphere
Weight
All outputs are relay outputs.
2 A, 250 VAC (cosφ = 1)
2 A, 24 VDC
(4 A/common)
10 mA, 5 VDC
Electrical: 300,000 operations (resistive load) 100,000 operations (inductive load)
Mechanical: 10,000,000 operations
15 ms max.
15 ms max.
Internal
Circuits
Do not connect loads or apply voltage in excess of the maximum switching
capacity to an output terminal. It may result in damage to the product or fire.
Converts between the CMOS format (PC CPU Unit side) and the RS-232C format
(peripheral device side).
The RS-232C (peripheral device side) is isolated by a DC/DC convertor and photocoupler.
Power is supplied from the PC CPU Unit.
0.3 A max.
38,400 bps max.
Total length:15 m max.
10 to 57 Hz: 0.075-mm amplitude
2
57 to 150 Hz: 9.8 m/s
(1G) acceleration in X, Y, and Z directions for 80 minutes each
(Time coefficient; 8 minutes × coefficient factor 10 = total time 80 minutes)
2
147 m/s
(15 G) three times each in X, Y, and Z directions
Operating: 0° to 55°C
Storage: –20° to 75°C
10% to 90% (with no condensation)
Must be free from corrosive gas
200 g max.
Specification
Output
LED
Specification
Section 2-1
OUT
OUT
COM
Maximum
250 VAC: 2 A
24 VDC: 2 A
21