Greenlee CM-600 Instruction Manual page 11

Clamp-on meter
Hide thumbs Also See for CM-600:
Table of Contents

Advertisement

Available languages

Available languages

Accuracy
Refer to "Specifications" for operating conditions and temperature coefficient.
Accuracy is specified as follows: (a percentage of the reading + a fixed amount)
at 23 C 5 C (73.4 F 9 F), 0% to 75% relative humidity.
Value
DC Voltage
AC Voltage
AC Current
(200 A range)
AC Current
(600 A range)
Resistance*
* Maximum open circuit voltage: 1 V
Continuity
Threshold: Tone sounds if the measured resistance is less than approximately 50 ,
and turns off when greater than approximately 300 .
AC measurements are average sensing, RMS calibrated.
AC accuracy is specified for sine waves only.
Range
0 to 600 V
0 to 600 V
0 to 199.9 A
0 to 400 A
400 to 600 A
0 to 2000
Accuracy
(0.8% + 1 V)
(1.2% + 3 V)
(1.9% + 0.5 A)
(1.5% + 5 A)
(2.5% + 5 A)
(1.5% + 2 )
Frequency
Range
N/A
40 to 500 Hz
50/60 Hz
50/60 Hz
50/60 Hz
N/A
CM-600
Input
Impedance
2 M
2 M
2 nF
N/A
N/A
N/A
11