Omron PROFINET IO CJ1W-PRM21 Operation Manual page 30

Controller unit
Table of Contents

Advertisement

CJ1W-PNT21 Unit components
Indicator
Colour
NS
Green
Network Status
Red
--
COMM
Yellow
--
100M
Yellow
Note
7-Segment Display
Status
IO Controller in normal operation
Initialising Unit at startup
Downloading new PROFINET Configuration to the Unit
The Unit encountered and error
PROFINET output data valid status
ON: Output data is valid.
Flashing: Output data is invalid.
Reserved
Error Code
3-1-4
Switch settings
Setting the Unit Number
14
Status
Meaning
ON
PROFINET IO data exchange with all active devices.
Flashing
PROFINET attempting to establish data exchange with all configured
devices.
ON
--
Flashing
The Unit 's PROFINET IO Configuration is not available or incorrect.
OFF
The Unit is in OFFLINE mode. PROFINET Communication is not possible.
ON
Ethernet communication is active.
OFF
Ethernet communication is not active.
ON
PROFINET IO data exchange with at least one active IO Device
OFF
No PROFINET data exchange with any of the active IO Devices.
Unless otherwise specified the frequency of a flashing LED is 1 Hz (50%
duty cycle).
The following table explains the status information of the 7-segment display.
/i
There is no priority in the error codes; all errors will be displayed in the order
they occur. All error codes consist of a combination of a letter and a number,
so they can be distinguished from the other state indications immediately.
The unit number is used to identify individual CPU Bus Units mounted on a
PLC. The unit number must be unique for each CPU Bus Unit. Selecting a
non-unique number for a CPU Bus Unit will prevent the PLC System from
starting correctly.
Display
Displays character
Lit
"r"
Displays character
Lit
"--"
Displays character
Flashing
"d"
Error code value
Lit
Left dot
Right dot
CJ1W-PNT21
UNIT
Setting range:
NO.
0 ~ F (Hexadecimal)
Figure 3.4: CJ1W-PNT21 Rotary switch
Section 3-1