AC output cable connection procedure

1. Refer to the dimension drawings in the PVS800-57B hardware manual
(3AXD50000048300[EN]).
2. Remove the shroud from the output power terminals.
3. Put the cable(s) into the cabinet.
4. If it is a shielded cable, prepare the cable ends and do the 360° grounding at the cabinet
entry. Connect the twisted shield of the AC output cable(s) to the cabinet PE (ground)
busbar with a cable lug.
5. Connect the phase conductors to terminals L1, L2 and L3.
6. If it is present, connect the separate PE/grounding conductor to the cabinet PE (ground)
busbar.
7. Install the shroud on to the output power terminals.
L1, L2, L3
AC output terminals
a
Cable lead-throughs
L1
L2
L3
a
Electrical installation 37