Download Print this page

Mitsubishi Melsec FX-2DA User Manual page 3

Special function block

Advertisement

1.1 External dimensions
Any connection to these terminals
may damage the FX-2DA.
M3.5 (0.14)
terminal screws
2
DC24V ±10% 130mA
+24V
*4
Class 3
Grounding
PC
(100 Ω or less)
Extension cable
*1 Use a twisted pair shielded cable for the analog
output. This cable should be wired away from
power lines or any other lines which could induce
noise.
*2 Apply 1-point grounding at the load side of the
output cable (class 3 grounding: 100 Ω or less). If
electrical noise is caused from grounding,
disconnect from grounding.
*3 If electrical noise or a voltage ripple exists at the
output, connect a smoothing capacitor of 0.1 to
0.47 µF, 25V.
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Weight : Approx. 0.5kg (1.1 lbs)
24V LED
Extension cable
D-A LED
and connector
63 (2.48)
73 (2.87)
Wiring
+15V
DC/DC
AG
converter
0V
-15V
FX-2DA special function block
*4 Connect the ground terminal on the FX-2DA with
the ground terminal on the base unit of the
programmable controller. Use class 3 grounding
on the base unit, if available.
Caution;
(a) The same output channel cannot drive current
and voltage output loads at the same time!
(b) Shorting the voltage output terminals may da-
mage the unit!
Dimensions : mm (inches)
Groove for
35mm (1.38)
wide DIN rail
2-5.5mm (0.22)
hole
10 (0.39)
95 (3.74)
Voltage output
CH1
Inverter,
V
+
etc.
V
-
*1
I
+
*3
*2
I
-
CH2
V
+
V
-
Current output
I
+
Recorder,
etc.
I
-
*1
*2

Advertisement