Full Gauge Controls EVOLUTION TC-900E 2HP Quick Start Manual

Full Gauge Controls EVOLUTION TC-900E 2HP Quick Start Manual

Digital controller for refrigeration and defrost

Advertisement

Quick Links

Have this manual in the palm of
your hand by FG Finder application.
1. DESCRIPTION
For frozen products, it automates the defrost processes according to the need of installation (smart
defrost). Its output relay directly controls compressors of up to 2HP and its defrost output has a current
capacity of 10A. The ambient temperature control has a normal setpoint and an economic setpoint,
apart from the fast freezing function and alarm functions indicating open door. It also features a digital
filter, intended to simulate a mass increase in the ambient sensor (S1), thus increasing its response time
(thermal inertia) and avoiding unnecessary drives of the compressor. It also includes a smart key, lock
system and a control functions shutdown mode.
Product complies with UL Inc. (United States and Canada) and NSF (
2. APPLICATION
• Cold Storage Rooms
• Display freezers
3. TECHNICAL SPECIFICATIONS
Power supply
Control temperature
Operating temperature
Load current (outputs)
Operating humidity
Dimensions (mm)
Dimensions of the clipping for fixing
of the instrument
4. INDICATIONS AND KEYS
Defrost indication LED
Fan indication LED
Compressor output
indication LED
Quick Access
Menu Key
Set key
e
TC-900
5. INSTALLATION - ASSEMBLING
Panel
(Side View)
ATTENTION
FOR INSTALLATIONS WHERE A SEALING IS REQUIRED TO
AVOID LIQUID CONTACT, THE CUT FOR THE CONTROLLER
MUST BE OF 70,5X29mm MAXIMUM. THE SIDE LOCKS MUST
BE FIXED SO IT PRESSES THE RUBBER SEALING AVOIDING
INFILTRATION BETWEEN THE CUT AND THE CONTROLLER.
5.1 INSTALLATION - ELECTRICAL CONNECTIONS
Connection 115 Vac
D1/S3
D2
5 6 7 8
9 10 11 12 13 14 15 16 17
1
2 3 4
e
TC-900
DIGITAL CONTROLLER FOR
REFRIGERATION AND DEFROST
Fast Freezing
Functions
Control functions
lockdown
shutdown
United States)
.
TC-900E 2HP: 115 or 230Vac ±10% (50/60Hz)
-50°C to 105°C / -58°F to 221°F
0 to 50°C / 32 to 122°F
COMP: 16(12) 2HP 240Vac
DEFR: 10A / 240Vac 2400W
FANS: 5(3)A / 240Vac
10 to 85 %RH (without condensation)
76 x 34 x 77 mm (WxHxD)
71 ± 0,5 x 29 ± 0,5 mm (see item 5)
Functions lock indication LED
Control functions shutdown
indication LED
Temperature unit indication LED
2HP
71
± 0,5
mm
Dimension of the clipping
for fixing of the
instrument in panel
Panel (Front View)
IMPORTANT
THE USE OF APPROPRIATE TOOLS IS ESSENTIAL TO AVOID DAMAGE
IN THE CONNECTION AT INSTRUMENT TERMINALS:
SCREWDRIVER SLOT 3/32''(2.4mm) FOR ADJUSTMENTS IN THE
SIGNAL TERMINALS;
SCREWDRIVER PHILLIPS #1 FOR ADJUSTMENTS IN THE POWER
TERMINALS;
115 Vac
2HP
IP 65
FRONT
Serial
Protection
programming
level
6. OPERATIONS
6.1 Quick Access Menu Map
To access or navigate the quick access menu using the
displaying the temperature. For every touch, the next function in the list is displayed. To confirm, use the
/
(short press) key.
FAST FREEZING (ON/OFF)
;
e
TC-900
2HP
ECONOMIC SETPOINT(ON/OFF)
;
e
TC-900
2HP
DEFROST (ON/OFF)
;
e
TC-900
2HP
FUNCTIONS LOCKDOWN
;
e
TC-900
2HP
CONTROL FUNCTIONS
(ON/OFF)
;
e
TC-900
2HP
NORMAL SETPOINT
;
Increase key
e
TC-900
2HP
6.2 Quick access keys map
When the controller is on temperature display, the following keys serve as a shortcut for the following
Decrease key
functions:
;
Pressed for 5 seconds: turn on/turn off the control functions.
/ <
Pressed for 2 seconds: setpoint adjustment.
Short press: displays process.
<
Pressed for 2 seconds: inhibits audible alarm.
<
Short press: display of minimum and maximum measurement records.
<
Pressed for 2 seconds: when displaying records, it cleans the history.
<
Pressed for 4 seconds: performs manual defrost.
;
Enters the quick access menu.
<
<
and
Enters the functions selection.
6.3 Basic operations
6.3.1Setting the desired temperature
To access the setpoints setup menu press
display followed by the normal setpoint set value. Use the
/
. Immediately, the message [SP-e] appears indicating the setting of the economic
pressing
setpoint. Again, use the
[----] indication signals the setup completion. The setpoints can also be adjusted individually in the
quick access menu.
Connection 230 Vac
D1/S3
D2
5 6 7 8
9 10 11 12 13 14 15 16 17
1
2 3 4
e
e
2H P
2H P
TC -9 00
TC -9 00
;
(short press) key while the controller is
/
for 2 seconds. The message [SP,,] will appear on the
>
<
or
>
<
or
keys to modify the value and confirm by pressing
230 Vac
evolution
COMPONENT
E251415
EXIT FUNCTION
;
e
TC-900
2HP
FUNCTION SELECTION
;
e
TC-900
2HP
ERASE MIN. AND MAX.
VALUES
;
e
TC-900
2HP
MIN. AND MAX. TEMPERATURE
RECORD
;
e
TC-900
2HP
ECONOMIC SETPOINT
;
e
TC-900
2HP
to modify the value and confirm by
/
. Finally, the
The sensor S1 (black)
must be in the ambient.
The sensor S2 (gray) must
be placed in the evaporator
through metallic cramp.

Advertisement

loading

Summary of Contents for Full Gauge Controls EVOLUTION TC-900E 2HP

  • Page 1 evolution TC-900 DIGITAL CONTROLLER FOR REFRIGERATION AND DEFROST IP 65 COMPONENT FRONT 2H P 2H P Have this manual in the palm of TC -9 00 TC -9 00 your hand by FG Finder application. Fast Freezing Functions Control functions Serial Protection lockdown...
  • Page 2 6.3.2 Fast Freezing 6.3.9 Stage of the process, elapsed time and temperature in sensors In the fast freezing mode the cooling output remains permanently activated, thus accelerating the S2 and S3 cooling or freezing process. This operating mode can be activated or deactivated in the quick access >...
  • Page 3 CELSIUS FAHRENHEIT Description Unit Standard Unit Standard F07] High ambient temperature alarm (S1) °C °F [,F08] Cooling time (interval between defrosts) min. min. [,F09] Minimum time for compressor on 0 (NO) sec. 0 (NO) sec. [,F10] Minimum time for compressor off 0 (NO) sec.
  • Page 4 F14 - Maximum defrost time: F30 - Temperature difference (S3-S1) below which the economic setpoint is activated: When the temperature difference between sensor 3 and sensor 1 is less than the value set in this This parameter is used to set the maximum allowed time for the defrost process. If at the end of this parameter, the controller starts operating in economy mode.
  • Page 5: Environmental Information

    Extension Frame F55 - Sensor S3 temperature indication offset: The Full Gauge Controls extension frame allows the installation of Evolution / Ri line with measures This function allows compensating for eventual deviations in the reading of sensor S3 temperature, 76x34x77 mm (dimensions of the clipping for fixing in the extension frame is 71x29mm) in varied situations, resulting from the change of sensor or modification of the cable length.