ZCVRB47 – Vented Chase – Style 2 – OPENING WITH GRILL
Grill Opening must be
within 2" of Enclosure Top
Grill Opening must be
within 2" of Enclosure Top
VENTILATION PLATES MUST BE REMOVED
FRAMING TO CEILING-
MINIMUM ENCLOSURE-
GRILLS AT FRONT AND
BACK
Each grill must be 105
square inches free air
minimum.
Both Chase Vent
Openings Must be in the
same Pressure Zone
(Room / Area)
MINIMUM ENCLOSURE-
GRILL AT FRONT
Grill must have a total of 105
square inches free air minimum.
MINIMUM ENCLOSURE-
SIDE GRILLS
Grills must have a total of
105 square inches free
air minimum.
NOTE: Sides of enclosure
must have equal sized grills.
105 square inches free air
NOTE: Sides of enclosure
must have equal sized grills.
Grill Opening must be
within 2" of Enclosure Top
FRAMING TO CEILING -
MINIMUM ENCLOSURE-
SIDE GRILLS
Grills must have a total of
minimum.
MINIMUM ENCLOSURE-
GRILLS AT FRONT AND
BACK
Each grill must be 105
square inches free air
minimum.
Both Chase Vent
Openings Must be in the
same Pressure Zone
(Room / Area)
MINIMUM ENCLOSURE-
GRILL AT TOP
Grill area must have a
total of 105 square
inches free air minimum.
23