8 Troubleshooting and Maintenance
 Error Descriptions
Event name
Sensor Communications Error
Meaning
An error occurred in a Sensor connection.
Source
EtherCAT Master Function Module
Error attributes
Level
Effects
User program
Indicators
EtherCAT NET RUN
---
System-defined
Variable
variables
None
Cause and
Assumed cause
correction
The Sensor is disconnected.
Attached
None
information
Precautions/
None
Remarks
Event name
Sensor Communications Has Not Been Established
Meaning
Communications has not been established with the Sensor.
Source
EtherCAT Master Function Module
Error attributes
Level
Effects
User program
Indicators
EtherCAT NET RUN
---
System-defined
Variable
variables
None
Cause and
Assumed cause
correction
A sensor is not connected.
Attached
None
information
Precautions/
None
Remarks
8 - 10
Source details
Minor fault
Recovery
Continues.
Operation
EtherCAT NET ERR
---
Data type
---
Correction
Connect the Sensor again and cycle
the power supply.
Source details
Minor fault
Recovery
Continues.
Operation
EtherCAT NET ERR
---
Data type
---
Correction
Connect at least one Sensor.
E3NW-ECT EtherCAT Digital Sensor Communication Unit Operation Manual (E429)
Event code
04C40000 hex
Slave
Detection
timing
Error reset (after
Log category
cycling the
power)
Input is not possible from the Sensor. The input data will
be 0.
EtherCAT LINK/ACT
---
Name
---
Prevention
Connect the Sensor securely.
Event code
04C50000 hex
Slave
Detection
timing
Error reset (after
Log category
automatic slave
recovery)
The input data will be 0. Safe-operational state and Oper-
ational state cannot be entered.
EtherCAT LINK/ACT
---
Name
---
Prevention
Connect at least one Sensor.
Continuously
System
When establish-
ing communica-
tions after turning
ON power to the
slave.