Field Settings On The User Interface - Daikin SEHVX20BAW Installation And Operation Manual

Split packaged air-cooled water chiller
Table of Contents

Advertisement

Setting
Refrigerant recovery/vacuuming mode.
This is a field setting of the outdoor module. In case of
SEHVX40+64BAW, perform the setting on both outdoor modules.
In order to achieve a free pathway to reclaim refrigerant out of the
system or to remove residual substances or to vacuum the system,
it is necessary to apply a setting which will open the required
valves in the refrigerant circuit so the reclaim of refrigerant or
vacuuming process can be done properly.
To stop the refrigerant recovery/vacuuming mode, push BS1. If
BS1 is not pushed, the system will remain in refrigerant recovery/
vacuuming mode.
6.1.9

Field settings on the user interface

The user can change the field settings using the user interface.
Each field setting is assigned a 3-digit number or code, e.g. [5-03],
which is indicated on the user interface display. The first digit [5] is
the 'first code' or field setting group. The second and third digit [03]
together are the 'second code'.
c
b
1 Press
for a minimum of 5 seconds to enter the field setting
mode.
Result:
(c), the current selected field setting code
(b) and the set value
2 Press
to select the appropriate field setting first code.
3 Press
to select the appropriate field setting second
code.
Operation ON/OFF
Setting the leaving water temperature
Setting the room temperature
Quiet mode ON/OFF
Weather dependent setpoint operation ON/OFF
Setting the clock
Programming the schedule timer
Schedule timer operation ON/OFF
Field settings
Error code display
Test operation
SERHQ020~032BAW1 + SEHVX20~64BAW
Split packaged air-cooled water chiller
4P508019-1C – 2018.04
(= binary)
(a) are displayed.
Master
(default)
4 Press
and
field setting.
5 Press
to save the new value.
6 Repeat the previous steps to change other field settings as
required.
7 When finished, press
INFORMATION
▪ Changes made to a specific field setting are only stored
when
code or pressing
▪ Field settings are grouped by their first code, e.g. field
settings [0-00]; [0-01]; [0-02]; [0-03] are defined as
a
"Group 0". When different values are changed within
the same group, pressing
changed within this group.
INFORMATION
▪ Before shipping, the set values have been set as
shown in
page 25.
▪ When exiting the field setting mode, " " may be
displayed on the user interface display while the unit
initializes itself.
[0] Remote control setup
[0‑00] User permission level
The user permission level defines which buttons and functions are
available for the user. By default no level is defined, so all buttons
and functions are operable.
[0‑00]
2
Permission level 2
3
Permission level 3
Slave
6 Configuration
Value
Description
Deactivated
Activated
to change the value of the selected
to exit the field setting mode.
is pressed. Navigating to a new field setting
will discard any changes.
will save all the values
"6.1.9 Field settings on the user interface" on
Description
Permission level 2
Permission level 3
Installation and operation manual