Table of contents 5.7.3 To insulate the water piping ......... 18 Table of contents Connecting the electrical wiring..........18 5.8.1 Field wiring: Overview..........18 5.8.2 To route and fix the power supply........ 18 5.8.3 To connect the power supply of the outdoor unit ..19 1 About the documentation 5.8.4 To connect the power supply and transmission...
This appliance is intended to be used by expert or trained Daikin website (publicly accessible). users in shops, in light industry and on farms, or for ▪ The full set of latest technical data is available on the Daikin commercial use by lay persons. extranet (authentication required).
3 About the units and options Heating About the units and options Identification 3.1.1 About the outdoor unit SERHQ outdoor units are designed for outdoor installation and are meant to be combined with SEHVX indoor units. The outdoor units are designed to work in heating mode at ambient temperatures from –15°C ...
Outdoor unit ▪ Foreign materials inside pipes (including oils for fabrication) must be ≤30 mg/10 m. ▪ Piping connection sizes Indoor unit Liquid Outdoor unit Liquid SEHVX20BAW Ø25.4 mm Ø12.7 mm 1× SERHQ020BAW1 Ø22.2 mm Ø9.52 mm SEHVX32BAW Ø25.4 mm Ø12.7 mm 1× SERHQ032BAW1 Ø28.6 mm...
4 Preparation Minimum water volume Model Minimum total water volume (l) INFORMATION In critical processes, or in rooms with a high heat load, extra water might be required. INFORMATION Water volume correction factor The temperature step difference can be modified using Temperature differential (K) settings [A‑02] and [F‑00].
SERHQ032BAW1 40 A field setting components" on page 22. Indoor unit Recommended fuses 5.1.3 To open the indoor unit SEHVX20BAW 6 A DANGER: RISK OF ELECTROCUTION SEHVX32BAW 10 A SEHVX40BAW DANGER: RISK OF BURNING SEHVX64BAW To gain access to the unit, front plates need to be opened as follows: NOTICE 4×...
5 Installation Not allowed Allowed ▪ The height of the foundation must at least be 150 mm from the floor. In heavy snowfall areas, this height should be increased, depending on the installation place and condition. ▪ The preferred installation is on a solid longitudinal foundation (steel beam frame or concrete).
5 Installation NOTICE Connecting the refrigerant piping ▪ When the installation height of the unit needs to be increased, do NOT use stands to only support the 5.4.1 Using the stop valve and service port corners. To handle the stop valve ▪...
5 Installation WARNING Take sufficient precautions in case of refrigerant leakage. If refrigerant gas leaks, ventilate the area immediately. Possible risks: ▪ Excessive refrigerant concentrations in a closed room can lead to oxygen deficiency. ▪ Toxic gas may be produced if refrigerant gas comes into contact with fire.
5 Installation 2 Connect a charge hose to service ports of all stop valves. 3 Recover gas and oil from the pinched piping by using a recovery unit. CAUTION Do not vent gases into the atmosphere. 4 When all gas and oil is recovered from the pinched piping, disconnect the charge hose and close the service ports.
▪ Use accessory pipes to connect field refrigerant piping to the piping connections on the indoor unit. For SEHVX20BAW, after cutting off the end of both the liquid and gas refrigerant piping, braze accessory pipe 1 to the liquid connection and accessory pipe 2 to the gas connection.
5 Installation ▪ Reinforce the insulation on the refrigerant piping according to the NOTICE installation environment. If operation is performed within 12 minutes after the indoor and outdoor units are turned on, the H2P LED will be lit Ambient Humidity Minimum thickness and the compressor will not operate before communication temperature...
5 Installation NOTICE In Europe, the greenhouse gas emissions of the total refrigerant charge in the system (expressed as tonnes CO equivalent) is used to determine the maintenance intervals. Follow the applicable legislation. Formula to calculate the greenhouse gas emissions: GWP value of the refrigerant ×...
5 Installation NOTICE ▪ Air in the water circuit can cause malfunctioning. During filling, it may not be possible to remove all the air from the circuit. Remaining air will be removed through the automatic air purge valves during the initial operating hours of the system.
5 Installation Power supply wiring (sheathed cable) (230 V) Transmission wiring (sheathed cable) (16 V) 5.8.3 To connect the power supply of the outdoor unit Power supply (400 V, 3N~ 50 Hz) Fuse Earth leakage breaker Grounding wire Power supply terminal block Electrical wiring Connect each power wire Wiring between units...
5 Installation Indoor unit The wiring for the other systems must be connected to the F1/F2 (Out-Out) terminals of the PCB in the outdoor unit to which the interconnecting wiring for the indoor units is connected. F1F2 Fixing the transmission wiring K1P K1S X4M F1F2 F1F2...
6 Configuration 5.8.6 To install the user interface The unit comes with a user interface offering a user-friendly way to set up, use and maintain the unit. Before operating the user interface, follow this installation procedure. Wire specification Value Type 2 wire CAUTION Section...
6 Configuration Initialisation: default situation What Changing the value of the ▪ Once mode 2 is selected (push BS1 NOTICE selected setting in mode 2 for more than 5 seconds) you can Be sure to turn on the power 6 hours before operation in select the wanted setting.
6 Configuration Value / Description Shows the status of power consumption limitation operation. Unit is currently not operating under power consumption limitations. Unit is currently operating under power consumption limitation. Power consumption limitation reduces the power consumption of the unit compared to nominal operating conditions.
6 Configuration Setting Value Description (= binary) Deactivated Refrigerant recovery/vacuuming mode. (default) Activated This is a field setting of the outdoor module. In case of SEHVX40+64BAW, perform the setting on both outdoor modules. In order to achieve a free pathway to reclaim refrigerant out of the system or to remove residual substances or to vacuum the system, it is necessary to apply a setting which will open the required valves in the refrigerant circuit so the reclaim of refrigerant or...
Page 26
6 Configuration After entering the field setting, the selected permission level must be enabled by simultaneously pressing , immediately 22°C 22°C followed by simultaneously pressing . Keep all 4 buttons 21°C 21°C 45°C 45°C pressed for at least 5 seconds. Note that no indication on the user 44°C 44°C 19°C...
Page 27
6 Configuration 22°C 22°C 21°C 21°C 21°C 45°C 45°C 44°C 44°C 19°C 19°C 19°C 19°C 19°C 19°C 18°C 42°C 42°C 42°C 42°C 42°C 42°C [2-01] [2-02] Normal room temperature setpoint 0:30 6:30 9:00 16:00 Room setback temperature [5-03] Time Temperature Setback configured for leaving water temperature control 18°C 18°C...
6 Configuration [9‑00] Leaving water temperature compensation value for [E‑03] heating operation This setting is not applicable. [9‑01] Leaving water thermistor auto corrective function [E‑04] Pump only operation (air purge function) This function will take into account the outdoor ambient conditions When installing and commissioning the unit it is very important to and correct the measured value which will be used for the logic.
7 Commissioning You read the complete installation and operation instructions, as described in the installer and user reference guide. A B C Installation Check that the unit is properly installed, to avoid abnormal noises and vibrations when starting up the unit. Field wiring A B C Be sure that the field wiring has been carried out...
7 Commissioning Airtightness test and vacuum drying Pump rotation direction Make sure the airtightness test and vacuum drying were If the 3-phase power input to the indoor unit is not completed. correctly wired (X1M), the pump may rotate in the wrong direction.
7 Commissioning ▪ The entering water temperature ( blink, and Final check flashes slowly). ▪ The indoor temperature ( blink). Before switching on the unit, read the following recommendations: ▪ The outdoor temperature ( blink). ▪ When the complete installation and all necessary settings have been carried out, be sure that all panels of the unit are closed.
8 Troubleshooting Main code Cause Solution No power is supplied to the outdoor unit. Check if the power wiring for the outdoor unit is connected correctly. The piping and wiring of the specified indoor unit are not Confirm that the piping and wiring of the specified indoor unit connected correctly to the outdoor unit.
9 Technical data Technical data A subset of the latest technical data is available on the regional Daikin website (publicly accessible). The full set of latest technical data is available on the Daikin extranet (authentication required). Service space: Outdoor unit...
9 Technical data Thermistor (suction) Wiring diagram: Outdoor unit Thermistor (coil-deicer) Refer to the wiring diagram sticker on the outdoor unit. The Thermistor (coil-outlet) abbreviations used are listed below: Thermistor (liquid-pipe receiver) INFORMATION Thermistor (accumulator) The wiring diagram on the outdoor unit is only for the Resistor (current sensor) (A4P) (A8P) outdoor unit.
12 Operation User interface ON/OFF button Operation 12.1 Operation range Use the system in the following temperature ranges for safe and effective operation. Cooling Heating Outdoor unit –5~43°C DB –15~35°C DB Indoor unit 5~20°C DB 25~50°C DB 12.2 Quick start-up The flow chart shows the steps required for starting up space cooling/heating and allows the user to start up the system before reading the entire manual.
12 Operation Select mode (heating h or cooling c) Push bi or bj Display: - starts to blink Display: "n" Set desired room temperature The remote controller room (e.g. 22°C) thermostat function is not installed Push ébi or ébj You have "room temperature You have "leaving water temperature based"...
12 Operation 12.3.2 About operating the system INFORMATION Setback operation and weather dependent setpoint are not If the main power supply is turned off during operation, operation will available in the cooling mode. restart automatically after the power turns back on again. 12.3.4 Space heating operation 12.3.3...
12 Operation 2 Press again to deactivate quiet mode operation. To switch space heating on/off using leaving water temperature control Result: disappears from the display. The actual temperatures can be displayed on the remote controller. In this mode, heating will be activated as required by the water temperature setpoint.
Page 43
12 Operation Space heating based on ON/OFF instruction Space heating based on temperature setpoint During operation When the schedule timer switches space During operation During schedule timer operation the operation heating OFF, the controller will be switched off LED is lit continuously. (operation LED will stop working).
Page 44
12 Operation 10 Select using to switch cooling and the remote INFORMATION controller off. Space cooling based on temperature setpoint is enabled 11 Repeat this procedure to program the other actions. by default, so only temperature shifts are possible (no ON/ OFF instruction).
Page 45
12 Operation To program quiet mode INFORMATION Press to return to previous steps in the programming procedure without saving modified settings. 1 Press to enter the programming/consulting mode. 2 Select the operation mode you would like to program using Result: The actual mode is blinking. 3 Press to confirm the selected mode.
13 Maintenance and service 2 Select the operation mode you would like to consult using 3 Press simultaneously for 5 seconds to delete the selected mode. Result: The actual mode is blinking. To delete a day of the week 3 Press to confirm the selected mode.
14 Troubleshooting WARNING Component Inspection Maintenance cycle cycle (replacements and/or Never replace a fuse with a fuse of a wrong ampere ratings repairs) or other wires when a fuse blows out. Use of wire or Electric motor 1 year 20,000 hours copper wire may cause the unit to break down or cause a fire.
Page 48
15 Relocation Malfunction Measure Main code Contents The remote controller ▪ Check if there is no power failure. Wait Insufficient supply voltage (indoor unit) display is blank. until power is restored. If power failure Two user interfaces are connected and both are set to occurs during operation, the system main (indoor unit) automatically restarts immediately after...
Page 52
4P508019-1 C 0000000 4P508019-1C 2018.04...
Need help?
Do you have a question about the SEHVX20BAW and is the answer not in the manual?
Questions and answers