Wiring A 48 V Dc Electrical Connector Block - Cisco N9K-C93128TX Hardware Installation Manual

Aci-mode switch
Table of Contents

Advertisement

Replacing Modules
• The power supply that you are installing must be capable of using the same airflow direction as the fan
• A DC power source must be within reach of the power cable that will be used with the replacement power
• There must be an earth ground connection to the chassis that you are installing the replacement module.
Step 1
Holding the replacement power supply with one hand underneath the module and the other hand holding the handle, turn
the power supply so that its release latch is on the right side and align the back end of the power supply (the end with
the electrical connections) to the open power supply slot before carefully sliding the power supply all the way into the
slot until it clicks into place.
If the power supply does not fit into the open slot, turn the module over before carefully sliding it into the open
Note
slot.
Step 2
If the DC power cables and a grounding cable are already connected to an electrical connector block, insert the block
into the power receptacle on the power supply.
If the electrical cables have not been connected to the electrical connector block, wire them as described in
V DC Electrical Connector Block, on page
Step 3
Turn on the circuit breaker for the DC power source connected to the power supply.
Step 4
Verify that the power supply is operational by making sure that the power supply
what the power supply LEDs indicate, see

Wiring a 48 V DC Electrical Connector Block

You must connect the ground, negative, and positive DC power cables to a connector block in order to connect
the power cables to a 48 V DC power supply.
Note
The recommended wire gauge is 8 AWG. The minimum wire gauge is 10 AWG.
Warning
<!--rcsi-show-stmt-number-->Statement 342 Before Connecting to System Power Supply
High touch/leakage current – Permanently connected protective earth ground is essential before connecting
to system power supply.
trays installed in the same switch
supply. If you are using n+n power redundancy, there must be a separate power source for each power
supply installed in the chassis (do not mix AC and DC power sources for the same switch). Otherwise,
only one power source is required.
Typically, the chassis is grounded by its metal-to-metal connection to a grounded rack. If you need to
ground this chassis by another means, see
45.
Power Supply LEDs, on page
Grounding the Chassis, on page
61.
Cisco Nexus 93128TX ACI-Mode Switch Hardware Installation Guide
Wiring a 48 V DC Electrical Connector Block