Airflow Requirements; Rack And Cabinet Requirements - Cisco N9K-C93128TX Hardware Installation Manual

Aci-mode switch
Table of Contents

Advertisement

Preparing the Site

Airflow Requirements

The switch is positioned with its ports in either the front or the rear of the rack depending on your cabling
and maintenance requirements. You must have fan and power supply modules that move the coolant air from
the cold aisle to the hot aisle in one of the following ways:
• Port-side exhaust airflow—Cool air enters the chassis through the fan and power supply modules in the
• Port-side intake airflow—Cool air enters the chassis through the port end in the cold aisle and exhausts
You can identify the airflow direction of each fan and power supply module by its coloring as follows:
• Blue coloring indicates port-side exhaust airflow.
• Burgundy coloring indicates port-side intake airflow.
• Gray coloring on DC power supplies indicates port-side exhaust airflow.
• Green coloring on DC power supplies indicates port-side intake airflow.
Note
To prevent the switch from overheating and shutting down, you must position the air intake for the switch in
a cold aisle. The fan and power supply modules must have the same direction of airflow (even if their coloring
is different). If you must change the airflow direction for the switch, you must shutdown the switch before
changing the modules.

Rack and Cabinet Requirements

You can install the following types of racks or cabinets for your switch:
• Standard perforated cabinets
• Solid-walled cabinets with a roof fan tray (bottom-to-top cooling)
• Standard open four-post Telco racks
• Standard open two-post Telco racks
Work with your cabinet vendors to determine which of their cabinets meet the following requirements or see
the Cisco Technical Assistance Center (TAC) for recommendations:
• Use a standard 19-inch (48.3-cm), four-post Electronic Industries Alliance (EIA) cabinet or rack with
• The depth of a four-post rack must be 24 to 32 inches (61.0 to 81.3 cm) between the front and rear
• Required clearances between the chassis and the edges of its rack or the interior of its cabinet are as
cold aisle and exhausts through the port end of the chassis in the hot aisle.
through the fan and power supply modules in the hot aisle.
mounting rails that conform to English universal hole spacing per section 1 of the ANSI/EIA-310-D-1992
standard.
mounting rails (for proper mounting of the bottom-support brackets or other mounting hardware).
follows:
Cisco Nexus 93128TX ACI-Mode Switch Hardware Installation Guide
Airflow Requirements
9