Fitting To Pre-Cast Flue Installations; Hearth Fitting; Spillage Monitoring System - Flavel REGENT FRLC EN Series Installation And Maintenance Instructions Manual

Battery ignition live fuel effect convector gas fire
Table of Contents

Advertisement

1.8.3

Fitting to Pre-Cast Flue Installations.

The appliance is suitable for use with pre-cast flues conforming to B.S.
EN 1858. The pre-cast opening must be a minimum of 122.7cm 2 or
equivalent cross-sectional area and have a minimum effective flue
height of 3 metres. The flue spigot restrictor must be removed when
installing into pre-cast flue applications
This appliance has been tested for use in a pre-cast flue block complying
with BS EN 1858. In accordance with BS EN 1858, pre-cast flues built with
directly plastered faces (front or rear) are not correctly installed as to ensure
proper operation with any type of gas fire. In some instances of this flue
construction, temperature cracking of surface plaster may occur through no
fault of the appliance. An air gap or some form of insulation material should
be installed to prevent normal flue temperatures from damaging wall
surfaces.
1.9

HEARTH FITTING

This appliance must only be installed on to a level concrete or non-
combustible hearth. The feet must not be removed when installing
directly onto a hearth.The hearth material must be a minimum thickness
of 13 mm with the top surface at least 50 mm above the floor level. The
hearth must be fitted symmetrically about the fire opening and have a
minimum width of 760 mm and a minimum projection of 300 mm
forwards from the fire opening.
1.10

SPILLAGE MONITORING SYSTEM

This appliance is fitted with an atmosphere sensing spillage monitoring
system in the form of an oxygen sensing pilot. This is designed to shut
the fire off in the event of partial or complete blockage of the flue
causing a build up of combustion products in the room in which the fire
is operating. The following are important warnings relating to the
spillage monitoring system:
The spillage monitoring system must not be adjusted by the
Installer. The spillage monitoring system must not be put out of action.
When the spillage monitoring system is exchanged, only a complete
original manufacturers part may be fitted. It is not possible to replace
individual parts on the pilot system on the appliance, only a complete
pilot assembly (including thermocouple) may be fitted.