Electro Industries EB-MX-10 Installation & Operating Instructions Manual

Electro Industries EB-MX-10 Installation & Operating Instructions Manual

Electro-boiler midsize

Advertisement

ELECTRO-BOILER
INSTALLATION & OPERATING INSTRUCTIONS
APPLICATION:
ACCESSORIES:
Note:
This product meets the requirements of the ASME Boiler and Pressure Vessel Code.
10/27/2016
Midsize
Model
EB-M(S or X)-10
EB-M(S or X)-15
EB-M(S or X)-20
This Electro-Boiler is factory equipped with WarmFlo smart controller.
WarmFlo automatically regulates outlet water temperature based on a desired
output temperature set point.
Primary application is any hydronic water heating system where reduced flow or
radiation can cause overheat conditions (example, zones). However, if it is a
mixture of large and small zones, the sudden capacity and flow changes may
cause some internal timing/over temp conditions. With the mixture of zones the
Electro Industries' zone controller option is highly recommended.
This series is equipped for load management interrupt and can apply to standard
baseboard radiation (not recommended for EB-MS Model), dual heat
combinations, under floor radiant, wood boiler supplement, etc.
Note: If this installation does not include dual heat standby boiler, the front panel
switch must always be in the "normal" position.
Attached BL001 lists various accessory or option items which are not part of
basic Electro-Boiler. See Room Thermostat Placement section for additional
information on slab stat.
BI516

Advertisement

Table of Contents
loading

Summary of Contents for Electro Industries EB-MX-10

  • Page 1 With the mixture of zones the Electro Industries’ zone controller option is highly recommended. This series is equipped for load management interrupt and can apply to standard baseboard radiation (not recommended for EB-MS Model), dual heat combinations, under floor radiant, wood boiler supplement, etc.
  • Page 2: Table Of Contents

    TABLE OF CONTENTS Description Page Introduction System or Water Flow Multiple Zones & Radiant Temperatures Zone Controller Room Thermostat Placement Two-Temperature Operation or Feature Multiple Boilers Boiler/Plumbing Kit Placement Installation Requirements Mechanical Installation Under-Floor Radiant Dual Heat Electrical Hookup Standby Boiler Water Fill Procedure Controller Setup Staging/Modulating Jumper...
  • Page 3: Introduction

    INTRODUCTION With this WarmFlo configuration, the electric heating elements are automatically staged/modulated and controlled to establish a fixed outlet water temperature. This outlet temperature is sensed by the WarmFlo controller and is controlled to achieve and maintain the boiler’s set point temperature. Even though this WarmFlo configured unit adjusts outlet temperature independent of water flow and prevents high limiting even with marginal water flow, it is still very important that the hydronic system be correctly designed for the building, the total heat loss requirement, and proper hydronics design and...
  • Page 4: System Or Water Flow

    2 GPM is required. Electro Industries’ Zone Controllers – the Electro Industries’ zone controller priority zone has the ability to communicate with this TS Series boiler and it will automatically switch to a low mass high water temperature (150 or 180) during zone 1, priority switch on, operation.
  • Page 5: Room Thermostat Placement

    a dial switch for each zone and the installer selects one of four zone capacity sizes. When dialing in the size closest to the zone Btu/h capacity, the zone controller “smarts” only allows the appropriate boiler stage which can handle that capacity. Also this is additive if more than one zone calls at any one time.
  • Page 6: Multiple Boilers

    MULTIPLE BOILERS This boiler series now includes a method for automatically staging any number of parallel-plumbed boilers. Order plug-in relay EB-C-STG5. The thermostat is connected only to the first boiler, when all stages are on for more than 5 minutes, this new plug-in relay module turns on the next boiler (R and W), and a second EB-C-STG5 could be used to turn on the third, etc.
  • Page 7: Boiler/Plumbing Kit Placement

    CSA/us certification label, and manufacturer product liability. Electro Industries, Inc., cannot be held responsible for field modifications, incorrect installations, and conditions which may bypass or compromise the built-in safety features and controls.
  • Page 8 3. Remember, safety is the installer’s responsibility and the installer must know this product well enough to instruct the end user on its safe use. Safety is a matter of common sense - - a matter of thinking before acting. Professional installers have training and experienced practices for handling electrical, sheet metal, and material handling processes.
  • Page 9: Mechanical Installation

    MECHANICAL INSTALLATION – UNDER-FLOOR RADIATION CAUTION Electro Industries Inc. requires the use of dielectric isolation between the boiler vessel supply and return piping when the boiler is plumbed using copper or any other dissimilar metal. Damage to the vessel caused by galvanic corrosion voids Electro Industries’ warranty.
  • Page 10 MECHANICAL INSTALLATION – DUAL HEAT CAUTION Electro Industries Inc. requires the use of dielectric isolation between the boiler vessel supply and return piping when the boiler is plumbed using copper or any other dissimilar metal. Damage to the vessel caused by galvanic corrosion voids Electro Industries’ warranty.
  • Page 11: Electrical Hookup

    ELECTRICAL HOOKUP Reference drawing BH511 1. 240 Volt Heating Power – route and install the proper current carrying conductors from service panel fuse or circuit breaker. See Specification Table and/or product nameplate for ratings. These models contain built-in circuit breakers and meet the requirement for local disconnect for appliances greater than 10 kW.
  • Page 12: Water Fill Procedure

    7. Zone Valves or Zone Pumps – see Zone Controller section for options. WARNING THE END SWITCHES FROM THE ZONE VALVES MUST BE AN ISOLATED CONTACT WITH NO VOLTAGE PRESENT ON THESE WIRES OR SCREW TERMINALS. THIS IS VERY IMPORTANT TO MAKE SURE THERE ISN’T ANY INTERFERENCE OR FEEDBACK BETWEEN THE TRANSFORMER OPERATING THE ZONE VALVE SYSTEM AND THE TRANSFORMER WITHIN THIS ELECTRO-BOILER PRODUCT.
  • Page 13: Controller Setup

    11. Close “water supply valve” and disconnect water supply. 12. Optional – energize circulating pump during this fill operation. The water pressure from the household system and as plumbed should typically flow through the circulating pump without the pump running. COMMENT: Purge one loop at a time.
  • Page 14: Staging/Modulating Jumper

    Staging/Modulating Jumper The control board on the Midsize Series boiler is a universal controller with the capability of interfacing with many different models of TS Electro boilers. The correct setting of this jumper is determined on the model of the boiler you are working with.
  • Page 15: Operational Tips

    OPERATIONAL TIPS Normal/Standby Switch  If this system does not have a standby operating (gas or oil) boiler, this switch must always be in the “normal” position.  To activate standby boiler, simply position front panel switch to “standby”. Monitor Lights, Front Panel ...
  • Page 16: Standby Switchover, Sot Timer

    Manual Reset, Hi-Limit At the top of the vessel there will be either two or three surface mount hi-limits preset at 205° F. There is no light indicator associated with these safety hi-limits. Also these 205° F safety limits break the L2 current carrying 240-volt wire going to the elements.
  • Page 17: Replacement Parts List

    Replacement Parts WFSB Water sensor, 3 ft. WFS25F Outdoor sensor (OT) EB5623 Controller, temperature sensing UFUSE0442 5-amp, fast blow mini-automotive fuse 4038KIT Triac switch module 5127 Heating relay 5535 Safety hi-limit, manual, 205° 5537 First hi-limit, auto-reset, 185° 5453 Relief valve, 30 PSIG 5456A Gauge press/temperature 5652...
  • Page 18: Troubleshooting/Repair Helps

    TROUBLESHOOTING/REPAIR HELPS 1. This WarmFlo controller contains several interference suppression components, but as an electronic logic product, unpredictable and unusual transients or interference may sometimes cause strange results. If the WarmFlo controller is “acting strange”, one immediate step would be power down reset.
  • Page 19 OPERATIONAL INFORMATION In order for the installer to completely understand the WF II functions and operational sequence it is recommended to thoroughly read and understand the information below. This knowledge can help in determining settings that can be set according to the end customer’s needs. WarmFlo Analyzer (WF-ANZ*) or PC software (ET-SOFT-HTG) –...
  • Page 21 NO. PART NUMBER DESCRIPTION QTY. EB-M*-** MECHANICAL PIPING EB-M*-** M-Series Electro-Boiler XTEE7060 1" X 1" X 1" TEE XNPL7780 1" X 2 1/2" NIPPLE XEL7850 Pipe Elbow 1" 90 Deg Black XBSH7180 1" X 3/4" BUSHING #5453 RELIEF VALVE #5595 AIR ELIMINATOR XBSH7190 1"...
  • Page 25 OILER CCESSORIES OILER CCESSORIES ZONE CONTROLLER This will simplify your wiring and make zoning applications much easier. In addition, enhanced communicating features have the ability to stage the electric boiler based upon the connected zone capacity. Pumps, Actuators, Valves Standard Features EB-ZTA-1 - install within boiler cabinet •...
  • Page 26: Bl001

    Electro Industries’ boilers come standard equipped with outlet temperature/pressure gauge, pressure relief safety valve, and when applicable, the WarmFlo electronic control sensors.
  • Page 27: Xx017

    Limited Product Warranty Effective November 1, 2009 Electro Industries, Inc. warrants to the original owner, at the original installation site, for a period of two (2) years from date of original purchase, that the product and product parts manufactured by Electro Industries, Inc.
  • Page 28 The decision whether to repair or, in the alternative, replace products or product parts shall be made by Electro Industries, Inc. or its authorized representative.