ELECTRO-BOILER
3-PHASE MODELS, 208-VOLT
INSTALLATION & OPERATING INSTRUCTIONS
APPLICATION:
This Electro-Boiler is factory equipped with WarmFlo smart controller.
WarmFlo automatically regulates outlet water temperature based upon outside
temperature and pre-setup parameters (commonly called "outdoor reset").
Primary application is any hydronic water heating system where reduced flow or
radiation can cause overheat conditions (example, zones). However, if it is a
mixture of large and small zones, the sudden capacity and flow changes may
cause some internal timing/over temp conditions. With the mixture of zones the
zone controller ZTS-* option is highly recommended (see page 2).
This series is equipped for load management interrupt and can apply to standard
baseboard radiation, dual heat combinations, under floor radiant, wood boiler
supplement, etc.
Note: If this installation does not include dual heat standby boiler, the front panel
switch must always be in the "normal" position.
ACCESSORIES:
Attached BL001 lists various accessory or option items which are not part of
basic Electro-Boiler. See Room Thermostat Placement for information on slab
stat. See Zone Controller section for information on a zone control update which
stages elements based upon zone capacity.
Note:
This product meets the requirements of the ASME Boiler and Pressure Vessel Code.
05/19/2016
TS Series
Model
EB-WX-13-2
EB-WX-27-2
BI515

Advertisement

Table of Contents
loading

Summary of Contents for Electro Industries EB-WX-13-2

  • Page 1 ELECTRO-BOILER TS Series 3-PHASE MODELS, 208-VOLT INSTALLATION & OPERATING INSTRUCTIONS Model EB-WX-13-2 EB-WX-27-2 APPLICATION: This Electro-Boiler is factory equipped with WarmFlo smart controller. WarmFlo automatically regulates outlet water temperature based upon outside temperature and pre-setup parameters (commonly called “outdoor reset”).
  • Page 2: Table Of Contents

    TABLE OF CONTENTS Description Page Introduction System or Water Flow Multiple Zones & Radiant Temperatures Zone Controller Room Thermostat Placement Multiple Boilers Two-Temperature Operation or Feature Boiler/Plumbing Kit Placement Installation Requirements Mechanical Installation Under-Floor Radiant Dual Heat Electrical Hookup Water Fill Procedure Controller Setup Operational Tips Replacement Parts List...
  • Page 3: Introduction

    INTRODUCTION With this WarmFlo configuration, the electric heating elements are automatically modulated and controlled to establish a fixed outlet water temperature. This outlet temperature is sensed by the WarmFlo controller and is controlled by outside temperature and by setup parameters. First-time or non-routine user –...
  • Page 4: System Or Water Flow

    2 GPM is required. Electro Industries Zone Controller – the Electro Industries zone controller priority zone has the ability to communicate with this TS Series boiler and it will automatically switch to a low mass high water temperature (150 or 180) during zone 1, priority switch on, operation.
  • Page 5: Room Thermostat Placement

    the size closest to the zone Btu/h capacity, the zone controller “smarts” only allows the appropriate boiler stage which can handle that capacity. Also this is additive if more than one zone calls at any one time. 3. Two temperature system with unbalanced zones – if the application includes zone one requiring high temperature (fin tube, air handler, etc.) and the remaining zones are radiant floor low temperature, this zone controller will automatically raise the output of the high temperature zone.
  • Page 6 Outdoor Reset Option The EB-WX-** boiler comes equipped with an outdoor sensor (shipped loose). This sensor can be connected to the board to allow for outdoor reset function. What is Outdoor Reset? Outdoor reset is where the Electro Boiler DT (desired water temperature) shifts up and down based on the outdoor temperature.
  • Page 7: Two-Temperature Operation Or Feature

    CSA/us certification label, and manufacturer product liability. Electro Industries, Inc., cannot be held responsible for field modifications, incorrect installations, and conditions which may bypass or compromise the built-in safety features and controls.
  • Page 8 with any needed installation of the gas/oil boiler, pump, plumbing, system design, hydronics systems or backup gas/oil boiler, etc. Any instructions or comments made within this manual (or factory phone assistance) relating to the gas/oil furnace are provided as comments of assistance and “helps” only.
  • Page 9: Mechanical Installation

    MECHANICAL INSTALLATION – UNDER-FLOOR RADIATION CAUTION Electro Industries Inc. requires the use of dielectric isolation between the boiler vessel supply and return piping when the boiler is plumbed using copper or any other dissimilar metal. Damage to the vessel caused by galvanic corrosion voids Electro Industries’ warranty.
  • Page 10: Dual Heat

    MECHANICAL INSTALLATION – DUAL HEAT CAUTION Electro Industries Inc. requires the use of dielectric isolation between the boiler vessel supply and return piping when the boiler is plumbed using copper or any other dissimilar metal. Damage to the vessel caused by galvanic corrosion voids Electro Industries’ warranty.
  • Page 11: Electrical Hookup

    ELECTRICAL HOOKUP Reference drawing BH513 1. 208 Volt Heating Power – route and install the proper current carrying conductors from service panel fuse or circuit breaker. See page 2 Specification Table and/or product nameplate for ratings. 2. Grounding – copper conductor is required, size per NEC code relating to the current of each feed. 3.
  • Page 12: Water Fill Procedure

    7. Zone Valves or Zone Pumps – see Zone Controller section for options. WARNING THE END SWITCHES FROM THE ZONE VALVES MUST BE AN ISOLATED CONTACT WITH NO VOLTAGE PRESENT ON THESE WIRES OR SCREW TERMINALS. THIS IS VERY IMPORTANT TO MAKE SURE THERE ISN’T ANY INTERFERENCE OR FEEDBACK BETWEEN THE TRANSFORMER OPERATING THE ZONE VALVE SYSTEM AND THE TRANSFORMER WITHIN THIS ELECTRO-BOILER PRODUCT.
  • Page 13: Controller Setup

    12. Optional – energize circulating pump during this fill operation. The water pressure from the household system and as plumbed should typically flow through the circulating pump without the pump running. COMMENT: Purge one loop at a time. CONTROLLER SETUP Red dial switch, front panel: Non outdoor reset –simply set the “knob”...
  • Page 14 Staging / Modulating Jumper The control board on the EB-WX Series boiler is a universal controller with the capability of interfacing with many different models of TS Electro boilers. With regard to the EB-WX boiler line, the “MODULATE” setting is the only available option for this jumper setting.
  • Page 15: Operational Tips

    OPERATIONAL TIPS Normal/Standby Switch  If this system does not have a standby operating (gas or oil) boiler, this switch must always be in the “normal” position.  To activate standby boiler, simply position front panel switch to “standby”. Monitor Lights, Front Panel ...
  • Page 16 Manual Reset, Hi-Limit At the top of the vessel there will be either two or three surface mount hi-limits preset at 205° F. There is no light indicator associated with these safety hi-limits. Also these 205° F safety limits break the L2 current carrying 208-volt wire going to the elements.
  • Page 17: Replacement Parts List

    Replacement Parts WFSB Water sensor, 3 ft. WFS25F Outdoor sensor (OT) EB5623 Controller, temperature sensing UFUSE0442 5-amp, fast blow mini-automotive fuse 4038 Triac switch module 5127 Heating relay 5535 Safety hi-limit, manual, 205° 5537 First hi-limit, auto-reset, 180° 5453 Relief valve, 30 PSIG 5456A Gauge press/temp.
  • Page 18: Troubleshooting/Repair Helps

    TROUBLESHOOTING/REPAIR HELPS 1. This WarmFlo controller contains several interference suppression components, but as an electronic logic product, unpredictable and unusual transients or interference may sometimes cause strange results. If the WarmFlo controller is “acting strange”, one immediate step would be power down reset.
  • Page 19 OPERATIONAL INFORMATION In order for the installer to completely understand the WF II functions and operational sequence it is recommended to thoroughly read and understand the information below. This knowledge can help in determining settings that can be set according to the end customer’s needs. Warning, field reprogramming –...
  • Page 28: Slab Stat

    OILER CCESSORIES OILER CCESSORIES ZONE CONTROLLER This will simplify your wiring and make zoning applications much easier. In addition, enhanced communicating features have the ability to stage the electric boiler based upon the connected zone capacity. Pumps, Actuators, Valves Standard Features EB-ZTA-1 - install within boiler cabinet •...
  • Page 29: Bl001

    Electro Industries’ boilers come standard equipped with outlet temperature/pressure gauge, pressure relief safety valve, and when applicable, the WarmFlo electronic control sensors.
  • Page 30: Xx024

    Electro Industries. If any product or product parts manufactured by Electro Industries are found to have manufacturing defects in materials or workmanship, such will be repaired or replaced by Electro Industries.
  • Page 31 ALL IMPLIED WARRANTIES, INCLUDING WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE, ARE HEREBY DISCLAIMED WITH RESPECT TO ALL PURCHASERS OR OWNERS. ELECTRO INDUSTRIES, INC. IS NOT BOUND BY PROMISES MADE BY OTHERS BEYOND THE TERMS OF THESE WARRANTIES. FAILURE TO RETURN THE WARRANTY CARD SHALL HAVE NO EFFECT ON THE DISCLAIMER OF THESE IMPLIED WARRANTIES.