Electro Industries EB-MA-10 User Manual

Electro-boiler

Advertisement

ELECTRO-BOILER
INSTALLATION & OPERATING INSTRUCTIONS
APPLICATION:
ACCESSORIES:
Note:
This product meets the requirements of the ASME Boiler and Pressure
Vessel Code.
Drawings:
BX505
BX504
BH510
BS510
BL001
XX017
09/15/2014
Midsize
Model EB-MA-10
This Electro-Boiler is factory equipped with WarmFlo smart controller. WarmFlo
automatically regulates outlet water temperature based upon preset, front panel,
temperature selection.
This model does not have an outdoor sensor and is not
programmed for outlet temperature ramping (outdoor reset concept). If your application
is "outdoor reset", you should be using model EB-MO series. This EB-MA series can
easily be field converted.
Primary application is any hydronic water heating system where reduced flow or
radiation can cause overheat conditions (example, zones). However, if it is a mixture of
large and small zones, the sudden capacity and flow changes may cause some internal
timing/over temp conditions. With the mixture of zones the zone controller ZEA-*
option is highly recommended (see page 2).
This series is equipped for load management interrupt and can apply to standard
baseboard radiation, dual heat combinations, under floor radiant, wood boiler
supplement, etc.
Note: If this installation does not include dual heat standby boiler, the front panel switch
must always be in the "normal" position.
Attached BL001 lists various accessory or option items which are not part of basic
Electro-Boiler. Also page 3 has additional information on slab stat.
EB-MA-15
EB-MA-20
BI509

Advertisement

Table of Contents
loading

Summary of Contents for Electro Industries EB-MA-10

  • Page 1 ELECTRO-BOILER Midsize INSTALLATION & OPERATING INSTRUCTIONS Model EB-MA-10 EB-MA-15 EB-MA-20 APPLICATION: This Electro-Boiler is factory equipped with WarmFlo smart controller. WarmFlo automatically regulates outlet water temperature based upon preset, front panel, temperature selection. This model does not have an outdoor sensor and is not programmed for outlet temperature ramping (outdoor reset concept).
  • Page 2: Table Of Contents

    TABLE OF CONTENTS Description Page Introduction System or Water Flow Multiple Zones & Radiant Temperatures Zone Controller Room Thermostat Placement Two-Temperature Operation or Feature Multiple Boilers Boiler/Plumbing Kit Placement Installation Requirements Mechanical Installation Under-Floor Radiant Dual Heat Electrical Hookup Standby Boiler Water Fill Procedure Controller Setup Operational Tips...
  • Page 3: Introduction

    INTRODUCTION With this WarmFlo configuration, the electric heating elements are automatically modulated and controlled to establish a fixed outlet water temperature. This outlet temperature is sensed by the WarmFlo controller and is controlled by preset, front panel, parameters. Even though this WarmFlo configured unit adjusts outlet temperature independent of water flow and prevents high limiting even with marginal water flow, it is still very important that the hydronic system be correctly designed for the building, the total heat loss requirement, and proper hydronics design and installation practices.
  • Page 4: System Or Water Flow

    2. Prevents over control or false staging up and down when the temperature sensors are attempting to regulate – since Electro Industries’ zone controller also has staging “smarts”, the addition of the zone controller will provide smoother boiler temperature control. The zone board has a dial switch for each zone and the installer selects one of four zone capacity sizes.
  • Page 5: Room Thermostat Placement

    The thermostat sensing bulb can later be pushed down this PVC conduit. If the slab is already poured without conduit for slab stat, use electronic remote sensing thermostat such as Electro Industries’ ES- 24-BR. These devices only require a ¼” hole drilled in the floor at some convenient location (preferably off a center wall, not within 2 feet of outside wall).
  • Page 6: Multiple Boilers

    CSA/us certification label, and manufacturer product liability. Electro Industries, Inc., cannot be held responsible for field modifications, incorrect installations, and conditions which may bypass or compromise the built-in safety features and controls.
  • Page 7 2. This installation manual and Electro-Boiler products relate only to the addition of the Electro-Boiler to the hydronics system. The owner/ installer assumes all responsibility and/or liability associated with any needed installation of the gas/oil boiler, pump, plumbing, system design, hydronics systems or backup gas/oil boiler, etc.
  • Page 8: Mechanical Installation

    MECHANICAL INSTALLATION – CAUTION Electro Industries Inc. requires the use of dielectric isolation between the boiler vessel supply and return piping when the boiler is plumbed using copper or any other dissimilar metal. Damage to the vessel caused by galvanic corrosion voids Electro Industries’ warranty.
  • Page 9: Dual Heat

    MECHANICAL INSTALLATION – DUAL HEAT CAUTION Electro Industries Inc. requires the use of dielectric isolation between the boiler vessel supply and return piping when the boiler is plumbed using copper or any other dissimilar metal. Damage to the vessel caused by galvanic corrosion voids Electro Industries’ warranty.
  • Page 10: Electrical Hookup

    ELECTRICAL HOOKUP Reference drawing BH510 1. 240 Volt Heating Power – route and install the proper current carrying conductors from service panel fuse or circuit breaker. See page 2 Specification Table and/or product nameplate for ratings. These models contain built-in circuit breakers and meet the requirement for local disconnect for appliances greater than 10 kW.
  • Page 11: Water Fill Procedure

    WARNING: The end switches from the zone valves must be an isolated contact with no voltage present on these wires or screw terminals. This is very important to make sure there isn’t any interference or feedback between the transformer operating the zone valve system and the transformer within this Electro-Boiler product.
  • Page 12: Controller Setup

    11. Close “water supply valve” and disconnect water supply. 12. Optional – energize circulating pump during this fill operation. The water pressure from the household system and as plumbed should typically flow through the circulating pump without the pump running. COMMENT: Purge one loop at a time.
  • Page 13: Operational Tips

    OPERATIONAL TIPS Normal/Standby Switch  If this system does not have a standby operating (gas or oil) boiler, this switch must always be in the “normal” position.  To activate standby boiler, simply position front panel switch to “standby”. Heating Cycle 1.
  • Page 14: Standby Switchover, Sot Timer

    Cold slab, outdoor reset and temperature sensing prevent full boiler on – by adding a temporary jumper between the lower W screw terminal and the upper left “E” tab, all temperature sensing functions are bypassed and the control board will step in all the stages. Caution: This jumper shall not be a permanent function, jumper needs to be removed after slab is approaching normal temperature.
  • Page 15: Troubleshooting/Repair Helps

    TROUBLESHOOTING/REPAIR HELPS 1. This WarmFlo controller contains several interference suppression components, but as an electronic logic product, unpredictable and unusual transients or interference may sometimes cause strange results. If the WarmFlo controller is “acting strange”, one immediate step would be power down reset.
  • Page 16 OPERATIONAL INFORMATION In order for the installer to completely understand the WF II functions and operational sequence it is recommended to thoroughly read and understand the information below. This knowledge can help in determining settings that can be set according to the end customers needs. WarmFlo Analyzer (WF-ANZ*) or PC software (ET-SOFT-TS) –...
  • Page 17 NO. PART NUMBER DESCRIPTION QTY. EB-M*-** MECHANICAL PIPING EB-M*-** M-Series Electro-Boiler XTEE7060 1" X 1" X 1" TEE XNPL7780 1" X 2 1/2" NIPPLE 1" 90deg ELBOW XEL7850 XBSH7180 1" X 3/4" BUSHING #5453 RELIEF VALVE #5595 AIR ELIMINATOR XBSH7190 1"...
  • Page 23: Slab Stat

    OILER CCESSORIES OILER CCESSORIES ZONE CONTROLLER This will simplify your wiring and make zoning applications much easier. In addition, enhanced communicating features have the ability to stage the electric boiler based upon the connected zone capacity. Pumps, Actuators, Valves Standard Features EB-ZTA-1 - install within boiler cabinet •...
  • Page 24: Bl001

    Electro Industries’ boilers come standard equipped with outlet temperature/pressure gauge, pressure relief safety valve, and when applicable, the WarmFlo electronic control sensors.
  • Page 25: Xx017

    TWENTY YEAR (20) LIMITED WARRANTY ON SPIN FIN ELEMENTS Electro Industries, Inc. warrants that the spin fin elements of its products are free from defects in materials and workmanship through the twentieth year following date of installation. If any spin fin elements are found to have a manufacturing defect in materials or workmanship, Electro Industries will replace them.
  • Page 26 ALL IMPLIED WARRANTIES, INCLUDING WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE, ARE HEREBY DISCLAIMED WITH RESPECT TO ALL PURCHASERS OR OWNERS. ELECTRO INDUSTRIES, INC. IS NOT BOUND BY PROMISES MADE BY OTHERS BEYOND THE TERMS OF THESE WARRANTIES. FAILURE TO RETURN THE WARRANTY CARD SHALL HAVE NO EFFECT ON THE DISCLAIMER OF THESE IMPLIED WARRANTIES.