When in zone screen
The zone screen will revert to the individual screen
automatically if nothing is done in it for one minute.
[Registration]
1.
Press the "ALL/INDIVIDUAL" button to
1
switch to the
2
2.
Using the arrow key,
3
to select the unit to be monitored.
"
"
Keeping the button pressed down will move it
rapidly.
The "
" lights up and the status of that unit
4
is displayed in the LCD. The cursor in the screen
Fig. 13 has selected unit 2-06.

Error diagnosing function

(Fig. 14)
This central remote controller is provided with a diag-
nosing function, for when an indoor unit stops due to
malfunction. In case of actuation of a safety device,
disconnection in transmission wiring for control or fail-
ure of some parts, the operation lamp, inspection dis-
play and unit No. start to flash; then, the malfunction
Operation
Maintenance
lamp
display
15
"INDIVIDUAL" screen.
move the
4
Malfunction
Unit No.
code
64
65
68
6A
6A
6F
6H
94
A0
A1
A1
A3
A6
A7
A9
AF
AH
AJ
code is displayed. Check the contents of the display,
and contact your DAIKIN dealer because the above
signs can give you the idea on the trouble area.
The display "
00 01 02 03
the group No. where the indoor
1
unit that has stopped due to mal-
2
function.
3
[Registration]
1.
Press the ARROW KEY BUTTON to call
1
up the group that has stopped due to mal-
function.
The unit No.
2
flashing because of an error failure.
C
Error content
Indoor air thermistor error
Outdoor air thermistor error
HVU error (Ventiair dust-collecting unit)
Dumper system error
Dumper system error + Thermistor error
Simple remote controller error
Door switch (Ventiair dust-collecting unit), relay harness fault
(Ventiair dust-collecting/humidifier unit)
Ventiair internal transmission error
(between total enthalpy – fan unit)
Indoor unit · external safety device error
Indoor unit · BEV unit (Sky-Air connection unit) PC board
assembly fault
Indoor unit · PC board assembly fault
Indoor unit · Drain level error (33H)
Indoor unit · Fan motor (51F) lock, overload
Indoor unit · Fan direction adjustment motor (MA) error
Indoor unit · BEV unit, electric expansion valve motor (20E) error
Indoor unit · Malfunctioning drain
Indoor unit · Dust-collector error
Indoor unit · Insufficient capacity setting, address setting fault
" flashes under
the malfunction code is
3
UNIT No.
L
English